WaterMaster
Electromagnetic flowmeter
2 Parameter Tables
IM/WMPBST–EN Rev. B
47
54 / 38
DO3_LOGIC_ACTION_STATE
Action state for Logic Output 3.
0: Normally Open
1: Normally Closed
Unsigned 8
1
S
r,w / C / a
Normally Open
55 / 39
VOLUME_AND_PULSE_UNIT
Units for totalizer and digital outputs.
1034: m3
1038: l
1040: ml
1041: hl
1043: ft3
1048: ugal
1049: igal
Unsigned 16
2
S
r,w / C / a
m3
56 / 40
PULSE_MODE
Pulse mode of digital outputs.
0: Pulse / Unit
1: Fullscale Frequency
Unsigned 8
1
S
r,w / C / a
Pulse / Unit
57 / 41
PULSE_WIDTH
Digital Output pulse width.
Min: 0.09
Max: 5000
Unit: mm
Float
4
S
r,w / C / a
5
58 / 42
LIMIT_FREQUENCY
Digital Output limit frequency.
Min: TB3.LIMIT_FREQUENCY_RANGE_LOWER
Max: TB3.LIMIT_FREQUENCY_RANGE_UPPER
Unit: Hz
Float
4
S
r,w / C / a
5250
59 / 43
FULLSCALE_FREQUENCY
Digital Output fullscale frequency.
Min: 0.25
Max: 10000000
Unit: Hz
Float
4
S
r,w / C / a
5000
60 / 44
PULSES_PER_UNIT
Digital Output pulse factor.
Min: 0.00001
Max: 10000000
Float
4
S
r,w / C / a
50
61 / 45
LIMIT_FREQUENCY_RANGE_LOWER
Limit frequency range lower value.
Unit: Hz
Float
4
D
r / C / a
0.25
62 / 46
LIMIT_FREQUENCY_RANGE_UPPER
Limit frequency range upper value.
Unit: Hz
Float
4
D
r / C / a
5250
Abs. Idx /
Rel. Idx
Variable Name / Brief Description
Data Type
Size
Store
Access /
Usage /
Transport
Default
Table 2.12 Slot 10 – Transducer Block 3 – Special Function (Continued)