WaterMaster
Electromagnetic flowmeter
2 Parameter Tables
IM/WMPBST–EN Rev. B
21
40 / 24
UNUSED
Unused parameter.
–
–
–
–
–
41 / 25
LO_LIM
Lower limit value for alarms with the same engineering unit as that of the OUT parameter.
If the measured variable is equal to or lower than the lower limit value, the State Bits in
the Status Byte of OUT and in the FB parameter ALARM_SUM are set to 1.
Float
4
S
r,w / C / a
–
42 / 26
UNUSED
Unused parameter.
–
–
–
–
–
43 / 27
LO_LO_LIM
Lower limit value for alarms with the same engineering unit as that of the OUT parameter.
If the measured variable is equal to or lower than the lower limit value, the State Bits in
the Status Byte of OUT and in the FB parameter ALARM_SUM are set to 1.
Float
4
S
r,w / C / a
–
44 / 28
UNUSED
Unused parameter.
–
–
–
–
–
45 / 29
UNUSED
Unused parameter.
–
–
–
–
–
46 / 30
HI_HI_ALM
The state of the upper limit of an alarm and the related time stamp. The time stamp
expresses the time the measured variable has been equal or higher than the upper limit
of the alarm.
DS-39
16
D
r / C / a
–
47 / 31
HI_ALM
The state of the upper limit of an alarm and the related time stamp. The time stamp
expresses the time the measured variable has been equal or higher than the upper limit
of the alarm.
DS-39
16
D
r / C / a
–
48 / 32
LO_ALM
The state of the lower limit of an alarm and the related time stamp. The time stamp
expresses the time at which the measured variable has been equal to or lower than the
lower limit of the alarm.
DS-39
16
D
r / C / a
–
49 / 33
LO_LO_ALM
The state of the lower limit of an alarm and the related time stamp. The time stamp
expresses the time at which the measured variable has been equal to or lower than the
lower limit of the alarm.
DS-39
16
D
r / C / a
–
50 / 34
SIMULATE
For commissioning and test purposes the input value from the Transducer Block to the
block can be simulated. Note that the Transducer block is disconnected from the block
when the SIMULATE parameter is in use.
DS-50
6
S
r,w / C / a
–
51 / 35
OUT_UNIT_TEXT
If the unit of the OUT parameter is not available in the list of PROFIBUS Unit Codes, the
user can write the specific text in this parameter. The unit code is then set to ’textual unit
definition’.
OctetString
16
S
r,w / C / a
–
Abs. Idx /
Rel. Idx
Variable Name / Brief Description
Data Type
Size
Store
Access /
Usage /
Transport
Default
Table 2.6 Slot 4 – Analog Input 2 – Internal Volume Forward Totalizer (Continued)