Electromagnetic flowmeter
2 Parameter Tables
IM/WMPBST–EN Rev. B
37
106 / 90
FACTORY_SENSOR_ZERO
Factory-set zero value.
Unit: mm/s
Float
4
D
r / C / a
0
107 / 91
TRIM_ST
Trim factor.
Unit: %
Float
4
D
r / C / a
0
108 / 92
SENSOR_CALIBRATION_TYPE
Sensor calibration type performed.
0: Retrofit
1: OIML Class 1
2: OIML Class 2
3: Special
4: OIML Certified Class 1
5: OIML Certified Class 2
6: Probe
7: NMI
8: Select
Unsigned 8
1
D
r / C / a
OIML Class 1
109 / 93
DRIVE_MODE
Drive mode currently in use.
0: User
1: 1
2: 2
3: 3
4: 4
5: 5
6: 6
7: 7
8: 8
9: 3A
10: 4A
11: 5A
12: 5B
13: 6A
14: 6B
15: 7A
16: 7B
17: 7C
18: 7D
19: 8A
20: 8B
21: 8C
Unsigned 8
1
D
r / C / a
5A
110 / 94
EXCITATION_CURRENT
Coil current value.
Unit: mA
Float
4
D
r / C / a
180
111 / 95
FACTORY_CUTOFF
Cutoff velocity set during calibration.
Unit: mm/s
Float
4
D
r / C / a
0
112 / 96
FACTORY_CUTOFF_NUM_AVERAGING_SAMPLES
Number of samples used in averaging filter.
Unsigned 8
1
D
r / C / a
4
113 / 97
CALIBRATION_STATUS
Sensor calibration status.
0: Not Complete
1: Calibrated
Unsigned 8
1
D
r / C / a
Not Complete
114 / 98
VOLUME_FLOW_RANGE_LOWER
Dynamic lower limit for flow values.
Unit: TB1.VOLUME_FLOW_UNITS
Float
4
D
r / C / a
0.5