WaterMaster
Electromagnetic flowmeter
2 Parameter Tables
IM/WMPBST–EN Rev. B
55
31 / 15
SIMULATION_LOGIC_3
State to simulate on Logic Output 3.
0: Off
1: On
Unsigned 8
1
D
r,w / C / a
Off
32 / 16
ELECTRODE_RESISTANCE_ALARM_MAX_EP
Upper limit of electrode resistance.
Min: 0
Max: 1000
Unit: kOhm
Float
4
S
r,w / C / a
200
33 / 17
ELECTRODE_RESISTANCE_ALARM_MIN
Lower limit of electrode resistance.
Min: 0
Max: 1000
Unit: kOhm
Float
4
S
r,w / C / a
0.1
34 / 18
ELECTODE_VOLTAGE_POSITIVE_LIMIT
Upper limit of electrode voltage.
Unit: V
Float
4
D
r / C / a
1.8
35 / 19
ELECTRODE_VOLTAGE_NEGATIVE_LIMIT
Lower limit of electrode voltage.
Unit: V
Float
4
D
r / C / a
–1.5
36 / 20
ELECTRODE_VOLTAGE_DIFFERENTIAL_LIMIT
Upper limit of differential electrode voltage.
Unit: V
Float
4
D
r / C / a
0.5
37 / 21
COIL_CURRENT_ALARM_BAND
Percentage shift in coil current allowed before alarm.
Unit: %
Float
4
D
r / C / a
1
38 / 22
COIL_OPEN_CIRCUIT_RESISTANCE_LIMIT
Upper limit of coil resistance range.
Unit: Ohm
Float
4
D
r / C / a
500
39 / 23
COIL_SHORT_CIRCUIT_RESISTANCE_LIMIT
Lower limit of coil resistance range.
Unit: Ohm
Float
4
D
r / C / a
5
40 / 24
SIMULATION_VOLUME_FLOW_RANGE_LOWER
Lower limit for internal simulated volume flowrate values.
Float
4
D
r / C / a
0
Abs. Idx /
Rel. Idx
Variable Name / Brief Description
Data Type
Size
Store
Access /
Usage /
Transport
Default
Table 2.14 Slot 12 – Transducer Block 5 – Diagnostics (Continued)