Modifications reserved
Page 6/15
ADDITIONAL AND USUAL INFORMATION
Connection
5 wires, 3 phase + N + PE
Cable entry
Bottom
Accessibility
Frontal only
Air outlet
Top
Color
Graphite Grey (RAL 7024)
Color code
PULVERLACKE NR.4222903402 Ver. 09RCCAT1 ORANGE PEEL
OPTIONS
Battery cabinets
Parallel Kit
SNMP Cards
USB port & Relay card with potential-free contacts (Customer outputs)
Back-feed protection
Single input feed KIT
Sea freight packaging (wooden box)
3
Input characteristics
PowerWave 33 Series 3
60
80
100
120
KW
Rated voltage
(steady-state, r.m.s)
380 / 220
400 / 230
415 / 240
VAC
Tolerance, referred to
400/230V
-10 / +15 at <100% load
-20 / +15 at <80% load,
-30 / +15 at <60% load
%
Frequency, rated
50
Hz
Tolerance, referred to 50Hz
-30 / +40
%
Current (r.m.s), rated
(with battery charged and input
400/230V)
92
122
152
183
A
Current (r.m.s), maximum
(with charging batt. and input
400/230V)
101
134
167
201
A
Total harmonic distortion
(THDi)
≤ 4% at 100% load
%
In-rush current
(A or % of nominal)
< 100% of the rated current
A or %
Power factor
0.99 @ 100% load
Rated short-time withstand
current (I
CW
)
10 for 1.5 seconds
kA, s
AC power distribution system: TN-S, TN-C, TN-C-S, TT
note: in static bypass mode or eco-mode TN-C and TN-C-S can cause PE current to rise above 5% of phase currents.
Phases required
3
Neutral required
yes