User manual |
PowerValue 11 RT 6-10kVA 43
Introduction
The battery configuration is described in the following way:
“number of battery strings” x ( “number of 12V battery blocks”
x “battery capacity”)
UPS internal battery configuration
UPS Model
Battery configuration
UPS PowerValue 11 RT 6 kVA
no internal
UPS PowerValue 11 RT 10 kVA
no internal
External Battery Module (EBM) battery configuration
EBM
Battery configuration
EBM for PowerValue 11 RT 6 kVA
1 x ( 15 x 9.0Ah )
EBM for PowerValue 11 RT 10 kVA
1 x ( 20 x 9.0Ah )
Standard EBM value setting through LCD display and RS232
(M is the total nr of standard EBM connected, M≥1)
UPS Model
LCD display (path: Settings
→
Password (USER)
→
External
battery modules)
RS232 (command:
SASV03[value]<cr>
PowerValue 11 RT 6 kVA
M*9/5 – 1
M*9/5
PowerValue 11 RT 10 kVA
M - 1
M
Settings with a customized battery pack of N Ah capacity,
through LCD display and RS232 (take only the integer part)
UPS Model
LCD display (path: Settings
→
Password (USER)
→
External
battery modules)
RS232 (command:
SASV03[value]<cr>
PowerValue 11 RT 6 kVA
N/5 – 1
N/5
PowerValue 11 RT 10 kVA
N/9 - 1
N/9
Appendix C: External Battery Modules (EBM) value calculation