32 PowerValue 11 RT 6-10kVA
| User manual
Submenu item
Description
Optional Values
Default value
Language
Select menu language
Chinese/English
English
User password*
Protects against settings modifications
enabled/disabled
disabled
Audio alarm
Enable/disable alarm sounds
enabled/disabled
enabled
Output voltage
Define local rated output voltage
208/220/230/240V
230V
Output frequency
Define local rated output frequency
autosensing/50/60Hz
autosensing
Power strategy**
or Running mode
Define the UPS running mode as normal, ECO-mode (or
HE high efficiency) and converter mode
normal/high efficiency/
converter
normal
DC start
Start the UPS from the batteries (without mains power)
enabled/disabled
enabled
Site wiring fault alarm
Phase and neutral cables are connected in reversed
positions.
enabled/disabled
enabled
Ambient temperature warning
Temperature is over the limit supported by the UPS
enabled/disabled
enabled
Automatic battery tests period
Define the frequency of the battery tests
0-31 days
7days
Auto restart
After UPS shuts down (low battery capacity), the UPS
restarts automatically when mains power is recovered.
enabled/disabled
enabled
Automatic overload restart
The UPS is automatically restarted if it shut downs due to
overload.
enabled/disabled
enabled
Auto bypass
Automatic bypass can be disabled for countries where the
power supply is very unstable. UPS runs only online or on
battery.
enabled/disabled
enabled
Short circuit clearance
- When enabled, short circuit will last for 4s before cutting
off the output. If short circuit is removed during this time,
the UPS will continue to run normally.
- When disabled, short circuit will only last for 100ms
before UPS output is cut off.
enabled/disabled
disabled
Redundancy lost (in parallel UPS
systems)
One of the parallel units has been disconnected from the
system
enable/disabled
enabled
Bypass voltage low limit
When the voltage in the bypass is below this limit, the UPS
changes running mode.
120~215V
184V
Bypass voltage high limit
When the voltage in the bypass is above this limit, the UPS
changes running mode.
245~276V
264V
Bypass frequency low limit
When the frequency in the bypass is below this limit, the
UPS changes running mode.
1%~10%
10%
Bypass frequency high limit
When the frequency in the bypass is above this limit, the
UPS changes running mode.
1%~10%
10%
ECO mode (HE) voltage low limit
When the voltage in the bypass is below this limit, the UPS
changes running mode.
5%~10%
5%
ECO mode (HE) voltage high limit
When the voltage in the bypass is above this limit, the UPS
changes running mode.
5%~10%
5%
ECO mode (HE) frequency low limit
When the frequency in the bypass is below this limit, the
UPS changes running mode.
1%~10%
5%
ECO mode (HE) frequency high limit
When the frequency in the bypass is above this limit, the
UPS changes running mode.
1%~10%
5%
External Battery module***
Define the number of battery modules. If number is higher
than 4, it should be configured through the monitoring
software
0-4
0
Set running time
Set the UPS running time mainly used for test purposes
Day:hour:minute:second
0000:0000:00~9999
23:59:59
Running time
LCD contrast
Changes the light contrast in the LCD panel
-5~+5
0
**Read Chapter 4.2, before using ECO-mode (HE mode) or converter function.
***Ensure that real battery quantity is same as the settings not to damage the batteries (see Appendix C).
Table 8: Settings menu
If the password is enabled, enter the password
USER
by
pressing the buttons , and
. The password is used
mainly to protect against unwanted modifications in the
Settings menu.
The available operations are listed in Table 8.