User manual |
PowerValue 11 RT 6-10kVA 33
Language
<English>
User password
<disabled>
Audio alarm
<enabled>
Output voltage
<230V>
Output frequency
<50Hz>
Power strategy
<normal>
DC start
<enabled>
Site wiring fault
<disabled>
Automatic battery tests
period
<7 days>
Auto restart
<enabled>
Automatic overload
restart
<enabled>
Auto bypass
<enabled>
Short circuit clearance
<disabled>
Ambient temperature
warning
<enabled>
Bypass voletage low
limit
<184V>
Bypass voltage high
limit
<264V>
Bypass frequency low
limit
<-5% (47.5Hz)>
Redundancy lost
alarm <enabled>
Bypass frequency high
limit
<+5% (52.5Hz)>
ECO mode voltage
low limit
<-5% (218.5.5V)>
ECO mode voltage high
limit
<+5% (241.5V)>
ECO mode frequency
low limit
<-5% (47.5Hz)>
ECO mode frequency
high limit
<+5% (52.5Hz)>
External battery modules
<0>
Set running time
LCD contrast
<0>
or
or
or
or
or
or
or
or
or
or
or
or
or
or
or
Parallel system
1 UPS system
or
or
or
or
or
or
or
Figure 37: Setting menu tree
Example: Setting the rated output voltage value (Figure
38). Note that the UPS must be in bypass to change this
parameter.
Figure 38: Setting rated output voltage value
Settings
Output voltage
<230V>
Output voltage
<230V>
Output voltage
<220V>
Output voltage
<220V>
Step 1: Scroll through the ‘Settings’ menu
Step 2: Select ‘output voltage’ submenu
Step 3: Change the value
Step 4: Confirm the setting
The setting stops flashing after confirmed
or
or