8
2TLC172011M0205_B
4 Gateway Default Configuration
4.1 Gateway Configuration
The Pluto gateway default configuration is very limited. The configuration is done on the gateway
by setting switch 1-2 of the DIP switch SW2. When this can be used is listed in the table below.
DIP-switch
1 2
Description
0
0
Only to read status from Pluto station 0 and 1.
0
1
Only to read status from Pluto station 0 – 7.
1
0
Only to read status from Pluto station 0 – 15.
1
1
Only to read status from Pluto station 0 – 31.
This configuration is current
not possible
to use because of limitations in the I/O
size in the ABB robotic system.
Note:
•
The ABB robotic system can with the “default” configuration mode only read data from
the connected Pluto system.
•
To be able to write data to the Pluto system you
can’t
use the “default” configuration
mode.
•
If the Pluto system has any Pluto with station number above 15 the “default”
configuration mode
can’t
be used.
4.2 Commissioning
During commissioning;
•
At ABB robotic system start it will do a DeviceNet IO connection with the gateway.
•
If the MNS LED is steady green the gateway is connected and normal operation.