Table 4:

Ethernet Configuration tabs

Tab

Description

Access points

This tab is used to configure access points.

The access point tab shows the access points

based on the supported hardware. For

example, if the 100FX-ST/100FX-LC hardware

modules are selected in hardware

configuration, the corresponding access points

will be available.

Merging unit

This tab is used to configure the merging unit.

Merging unit’s availability is based on the 9-2

order options and the hardware module

selection. For example, if OEM02 is selected,

the corresponding 9-12 merging units will be

available.

Routers

This tab is used to configure routers.

4.

Save the configuration data in one of the alternative ways.

Click the 

Save

 button on the toolbar.

On the 

File

 menu, select 

Save

.

Press CTRL+S.

5.5 

Using Graphical Display Editor

Graphical Display Editor is used for drawing the single-line diagram shown on the
graphical display of the IED. The diagram with its components corresponds to the
actual configuration.

1.

In 

Plant Structure

, select an IED.

2.

On the 

Tools

 menu, click 

Graphical Display Editor

.

The presentation is empty when no page exists for the IED. If standard
configurations are used, a default single-line diagram presentation is displayed.

3.

In the 

Symbol Library

 box, select either IEC or ANSI.

The symbols in the display pages and in the symbol library are changed.

4.

On the toolbar, activate the 

Snap to grid

 and 

Show grid

 functions.

5.

Create the single-line diagram.

5.5.1 

Creating single-line diagrams

1.

Add primary equipment to the display page by dragging from the 

Symbol

Library

.

Rotate the symbols with the Rotate left and Rotate right buttons on the
toolbar.

Select the size in the 

Symbol Size

 box.

2.

Add junction symbols for connections.

3.

Connect the symbols where necessary.

Section 5

1MRS757866 C

Use cases for engineering and commissioning

52

PCM600

Getting Started Guide

Summary of Contents for PCM600

Page 1: ... Protection and Control IED Manager PCM600 Getting Started Guide ...

Page 2: ......

Page 3: ...Document ID 1MRS757866 Issued 2018 04 18 Revision C Product version 2 9 Copyright 2018 ABB All rights reserved ...

Page 4: ...ed in this document is furnished under a license and may be used copied or disclosed only in accordance with the terms of such license Trademarks ABB is a registered trademark of the ABB Group All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders Warranty Please inquire about the terms of warranty from your nearest ABB re...

Page 5: ...ion of anti virus programs etc to protect the product and the network its system and interface included against any kind of security breaches unauthorized access interference intrusion leakage and or theft of data or information ABB is not liable for any such damages and or losses This document has been carefully checked by ABB but deviations cannot be completely ruled out In case any errors are d...

Page 6: ......

Page 7: ...ection 3 Getting started 13 Installing PCM600 13 Using Update Manager 13 Installing connectivity packages 13 Activating connectivity packages 14 Downloading IED preconfigurations and documentation 14 Installing language add on packages 15 Selecting the system language 15 Installing software packages on a computer that is not connected to the Internet 15 Customizing PCM600 menus 16 Managing users 1...

Page 8: ... Disturbance Handling 30 Reading recordings 31 Using Event Viewer 31 Filtering event data 31 Printing events 32 Exporting events to Excel file 32 Using Signal Monitoring 33 Section 5 Use cases for engineering and commissioning 35 Using Project Explorer 35 Creating new projects 35 Building the plant structure 35 Moving objects in the project tree 36 Creating IEDs 36 Creating IEDs from templates 36 ...

Page 9: ...nserting main applications from templates 46 Application Configuration shortcut keys 46 GOOSE Engineering 48 Enabling disabling GOOSE in Application Configuration 48 Making connections 48 Using Signal Matrix 48 Connecting binary inputs 49 Connecting binary outputs 50 Connecting analog input channels 50 Connecting analog output channels 50 Connecting GOOSE receive signals 51 Using Ethernet Configur...

Page 10: ...4 ...

Page 11: ...er security deployment guideline describes the process for handling cyber security when engineering and monitoring protection and control IEDs The cyber security deployment guideline provides information on how to secure the engineering environment on which the IED is installed The guideline can be used as a technical reference during the engineering phase installation and commissioning phase and ...

Page 12: ...zard which could result in corruption of software or damage to equipment or property The information icon alerts the reader of important facts and conditions The tip icon indicates advice on for example how to design your project or how to use a certain function Operation of damaged equipment could under certain operational conditions result in degraded process performance leading to information o...

Page 13: ...opy from the shortcut menu Click OK to start the comparing Shortcut keys are presented in uppercase letters A page can also be added pressing the shortcut keys CTRL SHIFT P Command prompt commands are shown in Courier font Type ping devices_IP_address t and wait for at least one minute to see if there are any communication breaks 1MRS757866 C Section 1 Introduction PCM600 7 Getting Started Guide ...

Page 14: ...8 ...

Page 15: ...s and functions and control the whole substation PCM600 is compliant with IEC 61850 which simplifies the IED engineering and enables information exchange with other IEC 61850 compliant tools The hierarchical presentation model that reflects the real system topology enables efficient viewing and editing of the power system information Some features and functions are product specific and not availab...

Page 16: ...ects must be imported from the connectivity package to PCM600 by using Upload Manager The Project Explorer window is used to navigate to the used IEDs within a project substation and to different functions within an IED A plant structure with a substation voltage levels bays and IEDs can be created in Project Explorer All the configuration work such as communication configuration can be done via t...

Page 17: ...ysical connections Disturbance Handling Disturbance Handling is used for uploading and processing the disturbance files located in a specific IED for viewing and processing the disturbance recording data and creating reports Ethernet Configuration Ethernet Configuration is used to configure the Ethernet ports both online and offline Ethernet configuration can be used to configure access points mer...

Page 18: ... performing tasks and functions in a PCM600 project PCM600 tools IED specific tools included in the connectivity packages The PCM600 tool documentation is included in the PCM600 online help The IED specific tool documentation is included in the related IED documentation Some features and functions are product specific and not available for all the products 2 3 PCM600 and IED connectivity package c...

Page 19: ...oftware Updates to display updates like PCM600 product updates connectivity packages and other general updates like add ons service packs and hotfixes Download and install the needed updates Select Export Software Packages to display all the available PCM600 add ons hotfixes and connectivity packages From this view it is possible to download the needed updates and export to another location remova...

Page 20: ...ctivity package version to be used and click Close 4 Restart PCM600 Restart is required to initialize the activated connectivity packages 3 5 Downloading IED preconfigurations and documentation Preconfigurations are available for some of the IED series For downloading the preconfigurations see the IED specific documentation The preconfiguration pcmi files are available on the connectivity package ...

Page 21: ...k OK PCM600 Language defines which language is used in the user interface of PCM600 Default IED Configuration Language determines the language of the IED specific content of newly created IEDs The drop down list contains all the languages supported by all the active connectivity packages If the used connectivity package does not support the selected language English is used The IED s language can ...

Page 22: ...ct the tools and functions to be shown in the menus Plus sign before the tool name indicates that the tool has functions for which the visibility can be separately defined Clicking the plus sign shows the tool functions 3 On the Options tab select the items to be visible in the Options dialog box 4 On the Miscellaneous tab define the visibility of miscellaneous menu items GUID 4C527940 8AD3 4930 A...

Page 23: ...ries For example a user category can be defined to have either read or read write access in Signal Matrix 1 On the menu bar click Tools and select Options to start the user management 2 Select the Category Manager folder 3 Click Add New Category to open the Add New Category dialog 4 Type the name for the new user category 5 Specify the rights to perform different functions under the Functions And ...

Page 24: ...er is created The new user name has to be a member of a user category to have permission to PCM600 functions 3 10 2 Managing IED users The IED User Management tool component is used for editing user profiles group memberships and group access rights for the IED functions and operations The availability of the tool functionalities depends on whether the IED has a full user management control built ...

Page 25: ...or information on resolving communication problems see Troubleshooting communication problems 3 11 Reporting The contents of each tool component can be viewed and printed On the menu bar click File and then click either Print or Print Review 1MRS757866 C Section 3 Getting started PCM600 19 Getting Started Guide ...

Page 26: ...20 ...

Page 27: ...data between two stand alone computers can be transferred All project related data is compressed and saved to one file which is named and located according to the definitions 4 1 2 Importing projects Importing a project enables transferring project data between the based systems via different media for instance in CD ROM The source and target computers do not have to be connected to the same netwo...

Page 28: ...d the Set Technical Key dialog box opens 4 In Set Technical Key dialog box select the techical key to be used Select one of the given alternatives Use the existing technical key in the IED Use the existing technical key defined for the IED object in PCM600 Set a user defined technical key which changes the technical key for both the physical IED and the IED object in PCM600 The maximum length of t...

Page 29: ... longer match Every relay communication card has a unique MAC address However for example in 615 series the front port IP address is fixed This can create a mismatched ARP table when several relays are used Windows also refreshes the ARP table automatically but this can take several minutes Click the Start button write cmd in the search box and press ENTER to open the command prompt Type arp d and...

Page 30: ... Time out property becomes visible Define the time out for long delay networks PCM communication uses the time out value specified by the user When selecting Fixed the default time out is used Does Online Configuration Wizard or reading configuration fail Make sure that your personal firewall allows inbound FTP connections Reading configuration files from certain IEDs requires the possibility for ...

Page 31: ...ls the operation The whole configuration is written to the IED The common writing from PCM600 to IED overwrites any parameter changes made locally using the LHMI 4 4 Using Parameter Setting Parameter Setting is used for parameterizing the IED units 1 In Plant Structure select an IED or a function 2 On the Tools menu click Parameter Setting Parameter Setting opens in the tool window and displays pa...

Page 32: ...lect Column autosize to autosize columns according to their content 4 On the View menu select Parameter warnings to enable displaying parameter warnings Warnings are displayed in the Output window in certain situations Modifying a parameter affects other parameters Parameter reading or writing fails for some parameter To find a parameter press the shortcut keys CTRL F 4 4 1 Setting parameters 1 In...

Page 33: ...eters are written to the IED not the whole configuration If the writing of a single parameter fails an error message is displayed Continue by choosing one of the given options Click Retry to write the parameter again Click Skip to skip the parameter Click Skip all to continue the writing of parameters and skip automatically the possible parameters that fail Click Cancel to end the writing procedur...

Page 34: ... and the Target group box and click OK All parameters currently visible in the setting sheet are copied from the source group to the target group 4 4 5 Collapsing and expanding parameter groups To collapse or expand a single group double click the parameter group header in the setting sheet Collapse or expand the selected group and it s child groups On the menu select View Group options Expand sel...

Page 35: ...e parameters To import all the parameters select the IED node To import the parameters related to a subnode select the subnode by expanding the IED node 2 Click the Import parameters toolbar button or on the File menu select Import parameters 3 Define the location of the import file The import file must be in xrio or csv format 4 Click Open and in the Open dialog box select the functions containin...

Page 36: ...ity to read the selected configuration and parameters 4 6 Using Disturbance Handling Disturbance Handling is used for uploading and processing the disturbance files gathered by a specific IED for viewing and processing the disturbance recording data and for creating reports 1 In Plant Structure click an IED 2 On the Tools menu click Disturbance Handling Disturbance Handling opens in the tool windo...

Page 37: ...in the shortcut menu Double click the IED recording The recordings with the IED icon enabled in the first column can only be read If a recording is already read in the local computer a warning appears asking if the recording should be overwritten 4 7 Using Event Viewer Event Viewer displays the actual or history events stored in the IED These events can be sorted and filtered for easier examinatio...

Page 38: ...on the main menu and click Filter On Off again The drop down list boxes below the column headers disappear When closing Event Viewer the filter settings are stored and applied when opening Event Viewer the next time 4 7 2 Printing events You can print the events that are currently displayed in Event Viewer You need to have a printer installed on the computer 1 On the File menu click Print Preview ...

Page 39: ... and select Signal Monitoring Signal Monitoring opens in the tool window 3 On the menu bar point to IED to select the monitoring option Click Read Latest Values From IED to read the values and update the view manually Click Toggle Continuous Reading to update the view automatically when new values are received Click Toggle Continuous Reading again to turn it off and click Forcing Session to test t...

Page 40: ...34 ...

Page 41: ...1 Create IED group or substation level objects 1 1 In Plant Structure right click a project and select New General and then select IED Group or Substation 1 2 Rename the IED group or substation by the name or identification used in the grid Right click the level and select Rename 2 Create voltage level objects 2 1 In Plant Structure right click a substation and select New General Voltage Level 2 2...

Page 42: ...ect the IED to be added 2 In the Configuration Wizard select the configuration mode and click Next Select Online configuration when the IED is already connected to PCM600 Select Offline Configuration when the IED is not available or is not connected to PCM600 3 Set up the IED following the steps in the Configuration Wizard The available steps and settings depend on the IED Communication protocol P...

Page 43: ...sting IEDs 1 In the Plant Structure right click the IED to be copied 2 On the shortcut menu click Copy 3 Right click the object level in Plant Structure for example a bay where the copied IED is to be inserted 4 In the shortcut menu click Paste The IED is now visible in the object tree Complete Bays or Voltage Levels can also be copied and pasted The keyboard shortcuts CTRL C and CTRL V can also b...

Page 44: ...d selecting Write to IED Click Yes to write the configuration data to IED Click No to cancel the operation You can rename the preconfigured IED in the Plant Structure by selecting the IED and pressing F2 The ordered default configurations are not locked and can be used as a base for other configurations providing that all the needed hardware and software options are available 5 1 9 Exporting IEDs ...

Page 45: ...s A main application is the drawing area for creating or editing the application configuration The main application can contain several pages A configuration always has one default main application On the Insert menu click MainApplication Click the Insert MainApplication button on the toolbar A new main application is created with the default name MainAppX where X is a sequential number 5 2 2 Copy...

Page 46: ...ent connections in the configuration 1 On the Insert menu point to Variable 2 Select Input or Output 3 Click the Application Configuration window to insert the variable The variable is inserted with its default name Variables can also be inserted using a shortcut menu in Application Configuration the View Variable List button on the toolbar or the shortcut keys CTRL SHIFT V 5 2 6 Inserting functio...

Page 47: ...d cannot be left empty If the maximum length is exceeded or unallowed characters are used an error message is shown 3 Click the Save button on the toolbar to save the new name Objects can also be renamed by right clicking a function block in Application Configuration and selecting Set User Defined Name or by pressing F2 5 2 8 Finding application objects In Application Configuration you can search ...

Page 48: ...ion to an existing or a new variable can also be created by selecting the signals and pressing the shorcut keys CTRL SHIFT E or CTRL SHIFT N 5 2 10 Deleting objects and unconnected variables The Delete Option dialog box allows deleting main applications pages Application Configuration symbols and unconnected variables from the configuration 1 On the menu bar click Edit and select Delete Option The...

Page 49: ...Align and select Left Right Horizontal Top Bottom Vertical to arrange the symbols in relation to the primary selected symbol Point to Align and select Detect overlapping FunctionBlocks to find the overlapping function blocks in the configuration The pages containing overlapping function blocks are listed on the Output window To locate a page double click an item on the list Point to Align and sele...

Page 50: ...ock or Unlock from the shortcut menu 5 2 14 Monitoring signal and channel values The signal and channel values of a configuration can be continuously monitored in the online monitoring mode of Application Configuration To online monitor the application configuration the complete IED configuration must first be written to the IED 1 On the toolbar click the Work online button to start online monitor...

Page 51: ... start the comparing A report is created about the differences in function blocks Also the missing blocks and connections are listed 5 2 17 Working with templates 5 2 17 1 Creating main application templates Main application configurations can be saved as templates and reused 1 Click the MainApp tab to select the main application to be saved as a template 2 On the File menu select MainApplication ...

Page 52: ...avigation of the selected variables CTRL TAB Go to the next main application CTRL SHIFT TAB Go to the previous main application RIGHT ARROW Move the selected objects to the right LEFT ARROW Move the selected objects to the left UP ARROW Move the selected objects up DOWN ARROW Move the selected objects down CTRL F Open the Find dialog box CTRL SHIFT V Open the Variable List dialog box CTRL SHIFT P ...

Page 53: ... help F2 Set the user defined name for the hardware channel Application key Open the shortcut menu of the hardware channel Picture selected F1 Open the PCM600 online help Application key Open the shortcut menu of the picture Signal selected F2 Set the user defined name for the signal CTRL SHIFT N Insert new variable on selection of signal CTRL SHIFT E Insert existing variable on selection of signa...

Page 54: ...ections 1 Right click the input signal of the function block point to Connect and select GOOSE to make a single GOOSE connection The Connect to GOOSE opens Input signals can be connected to the sender IED s IEC 61850 data attributes 2 In the Connect to GOOSE dialog box select the data attribute The Connect button is enabled After the input signal or channel has been connected to the data attribute...

Page 55: ...lue logic Normally only one source object can be connected to a target object Glue logic enables connecting several source objects to the same target object the outputs of multiple source objects are connected to the inputs of a simple boolean logic function and the output of the boolean function is connected to the target object The available boolean logic functions are AND and OR 5 3 1 Connectin...

Page 56: ...onnections between current and voltage channels and the input signals of current and voltage function blocks Double click an empty cell to create a connection Double click a cell with a symbol X to delete a connection Several analog input signals can be connected to the same physical analog input channel But once an analog input signal is connected to a physical analog input channel it cannot be c...

Page 57: ...al Matrix connection rules prevent incompatible connections Incompatible connection cells are disabled and shown in red 3 Click the Save button on the toolbar to save the connection changes 5 4 Using Ethernet Configuration Ethernet Configuration is used to configure the Ethernet ports both online and offline The Ethernet configuration can be started using the shortcut menu in the plant structure o...

Page 58: ...sed for drawing the single line diagram shown on the graphical display of the IED The diagram with its components corresponds to the actual configuration 1 In Plant Structure select an IED 2 On the Tools menu click Graphical Display Editor The presentation is empty when no page exists for the IED If standard configurations are used a default single line diagram presentation is displayed 3 In the S...

Page 59: ... be exported as templates and reused 1 Create a single line diagram in the Graphical Display Editor tool 2 On the menu bar point to Graphical Display Editor and select Export Display Pages as a Template or on the File menu point to Display Editor Template and click Export 3 Once the display page is selected click Export The File save dialog box appears 4 Browse the location to export the template ...

Page 60: ...tion mode 3 Click one of the tabs on bottom of the tool window to select the type of the configured data Data Sets GOOSE Controls Inputs Report Controls The type of the data available depends on the current configuration mode 5 6 1 Sending and receiving data In the Data Sets GOOSE Controls Report Controls and Sampled Value Controls tabs it is possible to configure the sending or receiving of data ...

Page 61: ...he PCM600 toolbar Press CTRL ALT N 2 Create a new object 2 1 In the tree on the left select the logical node where to create the new object 2 2 Type or select the required information in the fields on the right 2 3 Click OK or press ENTER to create the object Create new objects in the Subnetworks tab 1 Open the dialog box for creating a new object in one of the alternative ways On the Edit menu cl...

Page 62: ...o insert the data 2 Click Insert or press CTRL ALT I Remove the entries from the Data Set Entries list 1 Select the entries to be removed 2 Click Remove or press DELETE Move the entries up or down in the Data Set Entries list 1 Select the entry to be moved 2 Click Up or Down or press CTRL ALT UP ARROW or CTRL ALT DOWN ARROW Click OK or press ENTER to apply the changes The current number and the ma...

Page 63: ...data means only one entry and the current number of entries is increased by one 1MRS757866 C Section 5 Use cases for engineering and commissioning PCM600 57 Getting Started Guide ...

Page 64: ...58 ...

Page 65: ...EC International Electrotechnical Commission IEC 61850 International standard for substation communication and modeling IED Intelligent electronic device LD Logical device LHMI Local human machine interface LN Logical node MAC Media access control PC 1 Personal computer 2 Polycarbonate PCM600 Protection and Control IED Manager SCL XML based substation description configuration language defined by ...

Page 66: ...60 ...

Page 67: ...61 ...

Page 68: ...AASA Finland Phone 358 10 22 11 ABB AB Grid Automation Products SE 721 59 Västerås Sweden Phone 46 0 21 32 50 00 Fax 46 0 21 14 69 18 www abb com mediumvoltage www abb com substationautomation www abb com protection control Copyright 2018 ABB All rights reserved 1MRS757866 C ...

Reviews: