If the value is not valid, an error message is displayed describing the error and
correct format for the parameter.
If the changed parameter affects one or more other parameters and the parameter
warnings are on, the dependencies are displayed in the
Output
window.
3.
On the toolbar, click the Save button to save the change.
4.4.2
Writing parameters to an IED
In Parameter Setting, parameters can be written to an IED.
1.
In
Plant Structure
, select an IED.
2.
On the menu bar, click
IED
and select
Write parameters to IED
.
3.
In the
Write Parameters to IED
window, select the
Parameter range
and the
Parameter options
.
4.
Select
Read back
check box, if the parameters must be read back after writing.
5.
Click
OK
.
In Parameter Setting, only the parameters are written to the IED, not
the whole configuration.
If the writing of a single parameter fails, an error message is displayed. Continue by
choosing one of the given options.
•
Click
Retry
to write the parameter again.
•
Click
Skip
to skip the parameter.
•
Click
Skip all
to continue the writing of parameters and skip automatically the
possible parameters that fail.
•
Click
Cancel
to end the writing procedure.
Locked parameters are not written to IED before unlocking them.
The locked parameters must first be unlocked by right-clicking the
PC value
field and selecting
Unlock parameter
.
4.4.3
Copying parameter values
In Parameter Setting, parameter values can be copied from one or several parameters
to other/s. The copied parameter or parameter group has to be of the same type as the
target parameter or group.
1.
Select the parameter value or values.
1MRS757866 C
Section 4
Use cases for operation and field
PCM600
27