46 2CDC508171D0201 | SUG/U 1.1
3.4.4
Reaction on ETS reset
Input objects are initialized at 0. Exception: the object "Setpoint temperature" is initialized at 18 °C.
The value can differ from this if setpoint temperature limitation is active.
Status objects are sent according to the "Send status values after bus voltage recovery, download and
ETS reset" parameter on the "Status objects" page.
Sending delays parametrized on the "General" parameter page are taken into account.
IR commands to the split unit are always sent with the initialized values, irrespective of the parameter
"Reaction on bus voltage recovery, download and ETS reset".
Priorities are not active.
Timers (On/Off delay, window switching off delay, presence monitoring time, boost function duration) are
reset and the action set to occur when the timer has finished is executed.