ABB i-bus
®
KNX
Commissioning
SUG/U 1.1 | 2CDC508171D0201 39
No.
Function
Group object name
Data type
Flags
7
Status Operating mode
Split unit
1 byte
DPT 20.105
C, R, T
Dependent on parameter
Always visible
This object indicates the operating mode status for the split unit.
0=Auto
1=Heating
3=Cooling
9=Ventilation
14=Drying
8
Simplified Mode
Split unit
1 bit
DPT 1.100
C, W
Dependent on parameter
Enable "Simplified Mode"
This object switches between heating and cooling for basic applications.
1=Heating
0=Cooling
It is possible to operate the unit in parallel using object 6.
The operating mode status (object 7) is updated.
9
Silent Mode
Split unit
1 bit
DPT 1.002
C, W
Dependent on parameter
Enable "Silent Mode"
This object activates Silent Mode, provided the split unit supports it.
1=Activate Silent Mode
0=Deactivate Silent Mode
10
Status Silent Mode
Split unit
1 bit
DPT 1.002
C, R, T
Dependent on parameter
Enable "Silent Mode" and
Enable group object "Status Silent Mode" 1-bit
This object indicates the status of Silent Mode.
1=Silent Mode activated
0=Silent Mode deactivated
11
Scene
General
1 byte
DPT 18.001
C, W
Dependent on parameter
Enable "Scene" function
Using this 8-bit group object, a Scene telegram can be sent using a coded telegram.
The telegram contains the number of the scene concerned as well as the information on whether the scene is to be recalled or
stored.
The coding for this object is provided in Appendix 1.
Summary of Contents for i-bus KNX SUG/U 1.1
Page 1: ...ABB i bus KNX SUG U 1 1 Split Unit Gateway Product Manual ...
Page 2: ......
Page 4: ......
Page 52: ...ABB i bus KNX Appendix 50 2CDC508171D0201 SUG U 1 1 A 4 Notes ...
Page 53: ...ABB i bus KNX Appendix SUG U 1 1 2CDC508171D0201 51 Notes ...
Page 54: ...ABB i bus KNX Appendix 52 2CDC508171D0201 SUG U 1 1 Notes ...
Page 55: ......