KNX Technical Reference Manual
ABB-i-Bus
®
-KNX Millenium
Description of applications /
objects
KNX Technical Reference Manual | 1473-1-7819
— 32 —
Note
The following parameters are available only when parameter "Control type heating" is set on "PI
continuous", "PI PWM (1-bit)" or on "FanCoil".
General parameters for "Control
function = Heating"
Settings
Comments
Status object heating
•
deactivated
•
activated
–
Control type heating
•
2-point 1-bit (Off/On)
•
2-point 1-byte (0/100%)
•
PI continuous
•
PI PWM (1-bit)
•
FanCoil
–
Mode of the control value for heating
•
Normal
•
inverse
–
Hysteresis heating (1/10 K)
3 … 255
Only available when parameter "„Control
type heating" is set on "2-point 1-bit
(Off/On)" or "2-point 1-byte (0/100%)".
cyclical sending of the control value heating
(min)
1 … 60
–
Additional parameters for "Control
function = Heating"
Settings
Comments
Control parameter
•
via system type
•
Free paramaterization
–
Type of heating system
For "PI continuous"
and "PI PWM (1-bit)"
•
Hot-water heating
•
Electric heating
(1.5 K/50 min)
•
Floor heating (4
K/200 min)
–
For "FanCoil"
FanCoil (4 K/90 min)
P amount heating (1/10 K)
10 … 100
Only available when parameter "Control
parameter" is set on "Free
paramaterization".
I-component heating (min.)
0 … 255
max. control value heating
0 … 255
–
min. control value heating
0 … 255
–