KNX Technical Reference Manual
ABB-i-Bus
®
-KNX Millenium
Description of applications /
objects
KNX Technical Reference Manual | 1473-1-7819
— 54 —
Note
The following parameters are available only when parameter "Control type heating" or "Control
type cooling" is set on "PI continuous", "PI PWM (1-bit)" or "FanCoil".
General parameters for "Control
function = Heating"
Settings
Comments
Status object heating
•
deactivated
•
activated
–
Control type heating
•
2-point 1-bit (Off/On)
•
2-point 1-byte (0/100%)
•
PI continuous
•
PI PWM (1-bit)
•
FanCoil
–
Mode of the control value for heating
•
Normal
•
inverse
–
Hysteresis heating (1/10 K)
3 … 255
Only available when parameter "„Control
type heating" is set on "2-point 1-bit
(Off/On)" or "2-point 1-byte (0/100%)".
cyclical sending of the control value heating
(min)
1 … 60
–
General parameters for "Control
function" = cooling"
Settings
Comments
Status object cooling
•
deactivated
•
activated
–
Control type cooling
•
2-point 1-bit (Off/On)
•
2-point 1-byte (0/100%)
•
PI continuous
•
PI PWM (1-bit)
•
FanCoil
–
Mode of the control value for cooling
•
Normal
•
inverse
–
Hysteresis cooling (1/10 K)
3 … 255
Only available when parameter "„Control
type cooling" is set on "2-point 1-bit
(Off/On)" or "2-point 1-byte (0/100%)".
cyclical sending of the control value cooling
(min)
1 … 60
–