ABB i-bus
®
KNX
Parameters
ABA/S 1.2.1 | 2CDC509086D0201 87
7.10.31
RS Flip Flop (RS-FF)
Description
Stores input statuses and resets them on request.
Inputs
No. DPT
Abbr.
Name
Visible
Description
1
1 bit
S
Set
Always
A value of 1 sets the Flip Flop output to 1.
2
1 bit
R
Reset
Always
A value of 1 resets the Flip Flop output to 0
and disables it.
Outputs
No. DPT
Abbr.
Name
Visible
Description
1
1 bit
A
Output
Always
Flip Flop output status
2
1 bit
IO
Inverted Output
Always
Flip Flop inverted output status
Parameters
Initial value:
Initial value of the input. May only be used in combination with the
Set initial value after restart
parameter.
Note
Selecting the checkbox sets the initial value to 1, but only with 1-bit values. Deselecting the checkbox
(default) sets the initial value to 0.
Set initial value after restart:
The initial value is used after a restart.
Note
After a restart, either the initial values are used or the input values are restored, or the system waits for a
telegram to arrive. In the first two cases, the logic function is not recalculated.
Summary of Contents for i-bus KNX ABA/S 1.2.1
Page 1: ... PRODUCT MANUAL ABB i bus KNX ABA S 1 2 1 Logic Controller ...
Page 2: ......
Page 6: ......
Page 20: ......
Page 106: ......
Page 108: ......
Page 112: ......
Page 114: ...ABB i bus KNX Appendix 114 2CDC509086D0201 ABA S 1 2 1 13 2 Notes ...
Page 115: ...ABB i bus KNX Appendix ABA S 1 2 1 2CDC509086D0201 115 Notes ...