ABB i-bus
®
KNX
Parameters
86 2CDC509086D0201 | ABA/S 1.2.1
Inputs
No.
DPT
Abbr.
Name
Visible
Description
1
See above
I
Input
Always
2
See above
F
Factor
Parametrizable
3
See above
O
Offset
Parametrizable
Outputs
No.
DPT
Abbr.
Name
Visible
Description
1
See above
O
Output
Always
Parameters
Name
Value
Visible
Description
Factor
Single Float
Always
Enables
Factor
input
Offset
Single Float
Always
Enables
Offset
input
Calculation
•
The output is calculated as input * Offset.
•
If the output result is greater than the data type concerned:
the maximum for the data type is applied to the output.
•
If the output result is less than the data type concerned:
the minimum for the data type is applied to the output.
The N-CONV element can be used to divide a 2-byte unsigned value into an upper and lower byte.
•
The lower value is calculated using Factor = 1.
•
The unsigned upper 2-byte value is calculated using Factor = 0.00390625 (= 1/256).
•
The unsigned upper 4-byte value is calculated using Factor = 0.0000152587890625 (= 1/65536).
•
The conversion of a 1-byte unsigned value from a value range 0...255 into 0...100 is calculated using
Factor = 0.00390625.
Other
Unlinked inputs are treated as if they did not exist.
Summary of Contents for i-bus KNX ABA/S 1.2.1
Page 1: ... PRODUCT MANUAL ABB i bus KNX ABA S 1 2 1 Logic Controller ...
Page 2: ......
Page 6: ......
Page 20: ......
Page 106: ......
Page 108: ......
Page 112: ......
Page 114: ...ABB i bus KNX Appendix 114 2CDC509086D0201 ABA S 1 2 1 13 2 Notes ...
Page 115: ...ABB i bus KNX Appendix ABA S 1 2 1 2CDC509086D0201 115 Notes ...