![ABB i-bus KNX ABA/S 1.2.1 Product Manual Download Page 46](http://html.mh-extra.com/html/abb/i-bus-knx-aba-s-1-2-1/i-bus-knx-aba-s-1-2-1_product-manual_3072046.webp)
ABB i-bus
®
KNX
Parameters
46 2CDC509086D0201 | ABA/S 1.2.1
7.10.6
OR (OR)
Description
Logical OR link
Inputs
No.
DPT
Abbr.
Name
Visible
Description
1
1 bit
I
1
Input
Always
2
1 bit
I
2
Input
Always
3-16
1 bit
I
n
Input
Parametrizable
n = 3...16
Outputs
No.
DPT
Abbr.
Name
Visible
Description
1
1 bit
O
Output
Always
Note
An OR can be easily inverted to an NOR by double-clicking the output.
Parameters
Name
Value
Visible
Description
Input Count
2...16
Always
Function
Whenever a telegram is received the output starts a recalculation independently if the value has changed.
The output is 1 (true) if at least one input is 1 (true).
I
1
I
2
O
0
0
0
0
1
1
1
0
1
1
1
1
Other
Unlinked inputs are treated as if they did not exist.