Fig. 57 - Fuses installed (side)
Installing the fuses
a) Start installation from phase L3 (the one furthest from the
door).
b) The fuse striker pin must be facing upwards. First of all,
insert the entire lower part of the fuse into the bottom fuse
holder.
Fig. 56 - Installing the fuses
Fig. 58 - Fuses installed (front)
c) Push the upper part into the top fuse holder.
e) Close the door.
f) Turn the switch-disconnector to the “open” position and
then to the “closed” position (see chapter 5.12. Switch-
disconnector operating instructions).
d) Turn the fuse until the arrow and technical data texts are
no longer pointing towards the door.