Submenu/parameter
Value range
Comment
HART Date
03.11.2003
Day
Month
Year
Enter and output a date in this submenu.
No entry for standard devices (without HART hardware).
PA Adress
126
Numeric entry
0 - 125
2. PROFIBUS PA communication
Only available if PROFIBUS PA version was ordered.
Displays the slave address. Factory setting 126 (valid
addresses 0 - 125). The PA address can be set via the
following functions: Hardware switch (see chapter 6.4),
bus or the PA address menu. The hardware switch has
highest priority. The hardware switch setting has the
highest priority. An address using this setting switch
cannot be changed, either by bus or menu. If the switch
address is not active (DIP switch 8 = off), the address can
be changed via the bus or via the menu, however, only
when no cyclical communication is running.
DipSwitch
123456789A
- - - - - - -
Display only
Displays the settings for the DIP switches (- = OFF, X =
ON).
If DIP switch 8 = ON: The address is binary coded using
switches 1 - 7. Switches and 9 and A have no function.
Example: Set address 50 using the switches. 50dec =
32hex = 110010 binary
→
DIP switches 2, 5, 6 and 8 to
ON = PA address 50. The changed address switch setting
is only imported after the device is rebooted, not if
changed during normal operation. The factory setting of
the switch is: OFF
IdentNr Selector
FSM4000 0x078C
AI + 2* TOT
Setting the ID no. for the selector. It is not possible to
change modes during cyclical communication, but only in
STOP state.
Profile 0x078C: AI + 2* TOT (AI-Block + 2 Totalizer).
IdentNr Selector
Profile 0x9700
AI
Profile 0x9700 (AI-Block)
IdentNr Selector
Profile 0x9700
AI + TOT
Profile 0x9740 (AI-Block + Totalizer)
AI Channel
TB Flow Value
AI Channel
TB Total
→
V
AI Channel
TB Total
←
R
Channel setting for AI block. When setting the channel,
the unit for the channel is also copied to the AI block
(from OUT_SCALE. UNIT_INDEX).
Selection:
TB (Transducer Block) Flow Value
TB Total
→
F
TB Total
←
R
TB Diff Total
AI Channel
TB Diff Total