9
10
7
5
11
13
12
8
2
9
6
3
4
1
14
6. Structure
6.1. Drive structure
The drive is of the magnetic type and basically consists of the magnetic actuator (8) (fig. 4), the
control module (10), the current sensors (3), the capacitor/s (2) and the kinematics which transmit
the movement to the circuit-breaker poles.
The actuator (8) acts on the circuit-breaker poles by means of special kinematics. The capacitor/
s (2) provides/provide the energy required for the operation.
The mechanical operating positions of the circuit-breaker are detected by two due sensors (14).
The basic version of the circuit-breaker is fitted with the following controls and instruments:
• coupling for manual emergency operation (9)
• mechanical state indicator (6)
• mechanical operation counter (5)
• control panel (7) with opening and closing pushbuttons.
6.1.1. Structure of the control module
The control module (10) of the circuit-breaker consists of:
• a microprocessor
• opto-electrical input couplers
• output relay
• electronic power system for controlling the actuator coils.
1
Pole: vacuum interrupter
embedded in epoxy resin
2
Capacitor
3
Current sensor (Rogowski
coil)
4
Truck of withdrawable circuit-
breaker
5
Operation counter
6
Mechanical Open/Closed
signalling device
7
Control panel
8
Magnetic drive
9
Coupling for emergency
manual operating lever
10
Protection and control unit
11
Binary inputs/outputs
12
Communication
13
Socket for auxiliary circuits
14
Position Open/Closed
sensors
Fig. 4
Summary of Contents for eVM1
Page 1: ...eVM1 Installation and service instructions 12 17 5 kV 630 1250 A 16 31 5 kA ...
Page 2: ...1 ...
Page 76: ...74 Fig 66 Fig 67 ...
Page 77: ...75 Fig 68 Fig 69 ...
Page 110: ...108 Notes ...
Page 111: ...1 ...