105
14.14 Anomaly list
Whenever the IED detects an Anomaly condition the No Anomaly LED on the Local CB HMI
changes status from On to blinking. Active Anomalies can be displayed from the Panel HMI or from
the Monitoring tab by the Show pushbutton when an active communication link from a PC has been
established with the electronic Device (IED). Basic anomalies can be solved by the user and their
root cause and remedial action is described below.
Anomalies that require a higher skill and knowledge of the eCB are coded; the code will be given to
ABB service personnel to analyse and solve the Anomaly condition.
Some Anomaly conditions may be a block to the IED since critical information may be missing
preventing safely operating the CB (e.g. CB position sensor failure in open position).When a blocking
Anomaly is detected the IED goes permanently into Not ready status and will not operate. Resetting
the No Anomaly signal will clear only temporary Anomaly conditions; if the Anomaly persists the CB
will signal it again in real time.
Note
Classes
Shortdescription of
LCD Panel HMI
Anomaly
Anomalies
Code
CB anomaly
Call ABB Service with code
ANOMALY CODE
1
CB anomaly
Inconsistency among CB statuses
Error in CB status
2
Undefined CB status
3
CB anomaly
Reached max No. of opening attempts
Achieved max No. of
Opening attempts
4
IED anomaly
Call ABB Service with code
ANOMALY CODE
5
IED anomaly
Call ABB Service with code
ANOMALY CODE
6
ANOMALY CODE
7
ANOMALY CODE
8
IED anomaly
Call ABB Service with code
ANOMALY CODE
9
ANOMALY CODE
10
IED anomaly
Call ABB Service with code
ANOMALY CODE
11
ANOMALY CODE
12
CB panel missing
13
IO Board Missing
14
ANOMALY CODE
15
HMI device missing (CoT)
Comm. Error with CB (HMI)
16
IED anomaly
Call ABB Service with code
ANOMALY CODE
17
Panel anomaly
Inconsistency among CB truck statuses
CB TRUCK ERROR
18
CB TRUCK UNDEF
19
Panel anomaly
Inconsistency among Earthing Switch statuses
Earth Switch ERROR
20
Earth Switch UNDEF
21
CB anomaly
Wrong Position Autotrip performed
ERROR CODE
22
System anomaly
Energy Failure Autotrip performed
ENERGY FAILURE
AUTOTRIP
23
System anomaly
Opening due to UnderVoltage function
UV OPEN
24
Panel anomaly
Inconsistency among Line Disconnector statuses Load Disconnector ERROR
25
Load Disconnector
UNDEF (ONLY after 5s)
26
Load Disconnector ERROR
27
System anomaly
Configuration not allowed
Configuration not allowed
28
Panel anomaly
Auxiliary Supply failure
ANOMALY CODE
29