Tel: (888) 552-6467                             Fax: (800) 316-4515

11/22 750.2189 Rev.  B

4/12

EMIU 1500W Mini Inverter

 

  

a.   Unit can be configured for either 120V in // 120V out or 277V in // 277V out.
b. Power applied to the UNSWITCHED INPUT charges the batteries.
c. The SWITCHED INPUT can be configured to operate Normally-On, Normally-Off or Switched loads. 

d. Power supplied to the switched input must be fed from the same branch circuit as the unswitched input (see figure 2).

e. Unit is shipped from factory pre-set for 120V in // 120V out and configured for Normally-On load operation (see figure 2). This 

configuration can be changed to fulfill customer's application.   

f. In Normal AC mode, the load connected at the output is powered by the power applied to the SWITCHED INPUT. 
g. In Emergency mode, the load is powered by the battery through the inverter. The inverter converts the battery DC power to AC 

power. 

a.   Output voltage of the Mini Inverter can be configured for either 120VAC or 277VAC. 
b. Identify the terminal block TB1 located on the bottom of the electronic cabinet. 

c. Position of the red wire determines the voltage available at the output of the Mini Inverter. 

i. When the red wire is connected at the left terminal of TB1, the output voltage available will be 120VAC. 
ii. When the red wire is connected on the right terminal of TB1, the output voltage available will be 277VAC. 

d. Identify the voltage rating of all the loads to be powered by the Mini Inverter. 

i. If the voltage rating of the loads is 120VAC, connect the red wire to the left terminal of TB1.
ii. If the voltage rating of the loads is 277VAC, connect the red wire to the right terminal of TB1.     

a.   Connect the Ground wire to the Ground Bus Bar.
b. Identify the terminal block for UNSWITCHED INPUT (figures 5, 6 or 7). 
c. Connect the NEUTRAL wire to the NEUTRAL position of the UNSWITCHED INPUT terminal block.
d. Connect AC Line wire

i. 120V supply: connect AC line wire to the 120V position of the UNSWITCHED INPUT terminal block. 
ii. 277V supply, connect AC Line wire to the 277V position of the UNSWITCHED INPUT terminal block.   

 

 

     

ELECTRICAL SINGLE LINE DIAGRAM FOR EMIU 1500W SINGLE CIRCUIT

STEP 2: CONFIGURATION OF OUTPUT VOLTAGE (SEE FIGURE 2 AND 3)

STEP 3: WIRING TO UNSWITCHED INPUT

WARNING:

ENSURE THE BRANCH CIRCUIT BREAKER FEEDING THE UNIT IS TURNED OFF AT THE SERVICE 

PANEL BEFORE WIRING.

FIGURE 2

Circuit: Normally-ON

Normal Utility Panel

120V

Neutral

Ground

Neutral(Wht)

CHARGER

BATTERY

24VDC

INVERTER

120VAC(BLK)

277VAC(ORG)

SWITCHED INPUT

UNSWITCHED

INPUT

OUTPUT

HOT
NEU

120VAC(BLK)

Neutral(Wht)

Neutral(Wht)

120V(BLK)

277V(ORG)

F1

Mini Inverter comes pre-wired
for 120V. For 277V connections
remove red wire from
120V terminal and wire
to 277V terminal.

Transformer

Configuration:120Vin//120Vout

Orange

Black

Red

TO OBTAIN

120Vac OUTPUT

CONNECT RED WIRE 

POSITION TO OBTAIN 

TO OBTAIN

277Vac OUTPUT

Orange

Black

Red

FIGURE 3

TB1

TB1

CORRESPONDING OUTPUT VOLTAGE

TO APPROPRIATE 

3

4

Summary of Contents for EMIU 1500W

Page 1: ... 8 The use of accessory equipment and replacement parts not recommended by manufacturer may cause an unsafe condition and will void the warranty 9 Do not mount near gas or electric heaters 10 Do not let power supply cords touch hot surfaces 11 Do not use this equipment for other than its intended use 12 DO NOT USE OUTDOORS 13 The EMIU uses sealed valve regulated lead acid batteries Batteries can b...

Page 2: ...N OFF THE INVERTER MODULE WITHIN THE MINI INVERTER CAUTION ONLY ONE VOLTAGE IS ALLOWED 120V OR 277V CONNECTION TO MORE THAN ONE VOLTAGE MAY RESULT IN EQUIPMENT FAILURE AND VOID THE WARRANTY CAUTION THE MINI INVERTER HAS A SELF TEST FEATURE AND CAN ENTER IN SELF TEST MODE MONTHLY BIANNUAL OR ANNUAL AT ANY TIME WHEN THIS OCCURS POWER WILL BE AVAILABLE AT THE OUTPUT OF THE MINI INVERTER EVEN IF THE L...

Page 3: ...lts inside the battery cabinet g Mount the electronic cabinet securely to the wall using the keyhole slots at the rear of the cabinet h Route the blue and red wires through the two holes located at the bottom of the electronic cabinet to the battery cabinet i Connect the conduit containing the AC supply and remote fixture leads to the electronic cabinet Route the incoming wires through the knock o...

Page 4: ...ntify the voltage rating of all the loads to be powered by the Mini Inverter i If the voltage rating of the loads is 120VAC connect the red wire to the left terminal of TB1 ii If the voltage rating of the loads is 277VAC connect the red wire to the right terminal of TB1 a Connect the Ground wire to the Ground Bus Bar b Identify the terminal block for UNSWITCHED INPUT figures 5 6 or 7 c Connect the...

Page 5: ...ery 2 form the first string Battery 3 and Battery 4 form the second string The two 24V battery strings are connected in parallel c Route the RED positive and BLUE negative battery cables plus the thin yellow cable AWG 22 from the electronic cabinet to the battery cabinet d Connect the battery interconnect cables ALONG WITH THE THIN YELLOW CABLE AWG 22 e Measure the DC voltage between the yellow ca...

Page 6: ...wire from load to neutral terminal of output terminal block f The neutral of emergency fixtures must be wired to output terminal block g Do not connect the neutral wire of emergency fixtures to neutral wire of normal non emergency lighting fixtures h Connect hot wire from emergency lighting loads to the HOT terminal of OUTPUT terminal block a With loads connected follow the start up procedure in S...

Page 7: ...ery NORMALLY ON OPERATION Circuit configured to operate in Normally On mode Switched input Utility Neutral Ground NEUTRAL 120Vac 277Vac UNSWITCHED INPUT OUTPUT SELECT THE HOT LINE Neutral Hot CIRCUIT 1 Neutral Hot 120V TB1 LOCATION input FIGURE 5 NOTE WIRING DIAGRAMS ACTUAL POSITION OF COMPONENTS Configuration shown 120V in 120V out For 277V in 277V out connect utility hot wire to 277V position Un...

Page 8: ... 120V out CONNECT RED WIRE TO CORRESPONDING OUTPUT VOLTAGE APPROPRIATE POSITION TO OBTAIN Black Red TB1 Black Red Orange TO OBTAIN 120Vac OUTPUT TO OBTAIN 277Vac OUTPUT Orange NEUTRAL 120Vac 277Vac UNSWITCHED INPUT HOT LINE Neutral Hot CIRCUIT 1 Configuration shown 120V in 120V out For 277V in 277V out UNSWITCHED SWITCHED INPUT INPUT Important For 277 V output red wire must be removed from 120 V s...

Page 9: ...hen the unit ages Re initialization is not allowed if there is a lighting load failure alarm This is not applicable for units with No Auto Test plus No Load Detect option e SERVER FAILURE The Nexus server controller or PC is no longer communicating with the RF unit s modem Confirm Nexus server is operating and check whether other surrounding emergency lighting units are not powered If surrounding ...

Page 10: ...ide a 100 level of lighting The circuit consists of a single pole dry contact relay that is normally closed in stand by operation In emergency mode power failure the relay contacts open and disconnect the dimming signal from the lighting load allowing the load to operate at 100 light level INSTALLATION 1 Locate the Lighting Control signal cable pair 2 Cut strip and extend one wire only of the Ligh...

Page 11: ...ter module output fuse burnt out Check field wiring on mini inverter Ensure no voltage is being applied to the output of the mini inverter Replace fuse LED steady OFF not flashing Lamp load is ON No power at primary AC input in emergency mode Check position of breaker feeding the Mini Inverter in the breaker panel If breaker has tripped check for overload or short circuit See AC SPECS on page 1 La...

Page 12: ...ries Battery fail in charge Replace batteries LED Flashing RED 2 times every 6 seconds Charger Failure Charger not working Reset unit see page 7 If same error is displayed replace charger board LED Flashing RED 3 times every 6 seconds Lamp Failure Loss of 10 or more of initial lamp load Replace the bad lamp and reset the unit Lamp Failure No output voltage Fuses are burned out Verify output is not...