ABB | SACE Emax 2
Electrical accessories | 2 - Electrical signalling accessories
81 | © 2017
ABB |
1SDH000999R0002 - ECN000058721 - Rev. B
RTC: ready to close signalling
contact
RTC
48
46
45
The RTC contact indicates that the circuit-breaker is ready to receive a closing command.
The conditions necessary to allow the closing of the circuit-breaker are:
• circuit-breaker open
• springs charged
• absence of an opening command or of a lock in opening
NOTE:
if the circuit-breaker is opened due to the tripping of the Ekip protection trip unit, in
order to allow closing, the Reset signal of the circuit-breaker must have been reset (press
the TU Reset pushbutton on the front panel).
The RTC is a "switching" contact type and is available in the standard version or in the versions for digital
signals.
The following table provides information on the electrical characteristics:
Characteristics
Standard
Digital signals
Breaking
capacity
DC
24V
-
0.1 A
125V
0.3A @ 0ms
-
0.15A @ 10ms
-
250V
0.3A @ 0ms
-
0.15A @ 10ms
-
AC
125V - 250V
1A cos
φ
0.3
-
2A cos
φ
0.7
-
3A cos
φ
1
-
Minimum load
100mA @ 24V
1mA @ 5V
RTC: Connections
Further information is available on page 59, or on the site http://www.abb.com/abblibrary/DownloadCenter/,
where the wiring diagram is available
.
A4
X
XV
X
XV
A1
A4
RTC
45
48
45
45
48
48
46
46
46
1
XB6
3
XB6
2
71
Diagram 71
Information on the assembly is available on the web site http://www.abb.com/abblibrary/DownloadCenter/,
in particular with the kit sheet
.