L3447
Emax DC
43/108
Model
Scale
Page No.
Doc. No.
Apparatus
1SDH000635R0002
L3728
Protection
Parameter / Function
OT
Enable Trip
ON / OFF
Load Control
Threshold 1
Enable
ON / OFF
Threshold
Threshold 2
Enable
ON / OFF
Threshold
Threshold lw
Enable
ON / OFF
Threshold
Note: for an explanation of the characteristics of the single protections and their settings and corresponding curves, see par. 12.2.9.
12.5.3 Measurements Menu
The following is a summary of the parameters accessible from the menu in the PR122/DC unit.
12.5.3.1
Measurements Menu table
Setting
Parameter / Function
Values
Notes
Historicals
Trips
Last trips (20)
Events
Events log (80 events max.)
Measurements
I Max
Current
Reset measurements
Contact wear
Percentage of wear on CB contacts
12.5.4 Settings Menu
The configuration parameters in the Settings menu are password protected.
3/5
Protections settings
Measurements
Protections
Menu
Settings
1/9
Circuit breaker settings
Hw Trip
Modules
Circuit Breaker
Settings
Installation
Circuit Breaker
Install
Circuit Breaker
2
1/2
Uninstall
Enter
↵
Enter
↵
+ PWD
Parameter / Function
Values
Notes
Circuit breaker
Installation
Install/Uninstall
Hw trip
Enable-Disable
Modules
Module
PR120/D-M - COM
if any
see par. 12.5.4.2.1
PR120/K - Signalling
if any
see par. 12.5.4.2.2
Local Bus unit
Absent - Present
Data logger
Enable
ON/OFF
Sampling frequency
Stop event
Stopping delay
Restart
Stop
Measurement
from 5 to 120 min, step 5 min
interval
System
Date
Time
Language
English/Italiano/Français/Deutsch/Español
New password
Display
Contrast
12.5.4.1
Settings Menu table
The summary table relates to the surfing of the pages dedicated to the PR120/K module (see par. 14.3) and to the PR021/K unit (see par. 15.1).