Generator ON Facilities
The Generator ON facility must use a normally open contact that closes to indicate that a generator is running and
supplying input power to UPS. It is located at the bottom of the
DPA UPSCALE
TM
frame on communication card
with terminal blocks X1 …X
2. See section 3 / 1.2.1 for details
When used, this facility disables the UPS static bypass and prevents the UPS from transferring the load onto the
generator power supply.
Generator alarm panel
UPS
Generator port
X1
Figure 1.3: Generator ON Connection
9.1.4
Wavemon Shutdown and ManagementSoftware
9.1.4.1
Why is UPS Management important?
By combining a UPS with network management products, such as an SNMP protocol, System-administrators are
guaranteed their data and their system will constantly be protected from corruption or data loss even in the event of
an extended power failure or when batteries reach a critical low state. In the event of a power disturbance system
administrators can also monitor their network from a central location, allowing an early detection of problems. In
fact utility power is unreliable at times, ensuring that all network systems have constant power can be a difficult
task. The situation becomes even more complex if systems are managed across a Local Area Network (LAN) or
Wide Area Network (WAN) around the world.
When a power failure occurs action can be taken to protect the system and its valuable data. If no action is initiated
by the operator, this event can seriously damage the system. The UPS software will react automatically in such a
case and shutdown the operating system. The manufacturer has found it important to have a complete solution for
its UPS and is able to offer a wide range of monitoring/remote controls for assuring the maximum protection degree
to the customers.
9.1.4.2
WAVEMON Shutdown and Monitoring Software
WAVEMON Software
is an external monitoring and shutdown software which was designed to operate with all UPS
products, both with the DRY PORT (Relays) on Terminal block X1 and RS232 port JD1 on the communication card
The software packet consists of a CD ROM for most diffused operating systems (Windows, Unix, OS/2, DEC VMS,
Novell, Apple), a standard connection and a user manual.
The dry port
X2…X4
with voltage-free contacts may also be used for automatic shutdown in connection with
WAVEMON Software
. It is necessary to provide a cable of 0.5 mm2 to connect Terminals X1 of the UPS and the
serial port of the server.
X1/1
X1/2
X
1
X
2
Summary of Contents for DPA Upscale RI Series
Page 27: ......
Page 28: ......
Page 29: ......
Page 31: ......
Page 32: ......
Page 33: ......
Page 35: ......
Page 36: ......
Page 37: ......
Page 39: ......
Page 40: ......
Page 41: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 47: ......
Page 48: ......
Page 49: ......
Page 51: ......
Page 52: ......
Page 53: ......