Section-1
04-3006_S1_OPM_ABB_DPA_UPSCALE_RI_10-80kW_EN_150316.doc
Page 17/52 ABB
Modifications reserved
Subrack type
RI 10
RI 11
RI 12
RI 20
RI 22
RI 24
RI 40
Accessibility
Totally front accessibility for service and maintenance
Clearances
Back clearance of min. 20 cm required for hot air outlet. Cold air inlet is from front.
Positioning and mounting
see operating manual, Section 1 for details and mounting instructions.
Input and Output Cabling
From the bottom on the rear side.
1.5.3 ASSEMBLING INSTRUCTIONS
Please make sure that the 19” Rack has a structure with minimu
m structure with four post system (see fig.
2.1 -2.7)
Please make sure that the four post system can hold the weight of the total UPS system. Refer to the table
below.
Position and air cooling flow at the 19” Rack. Please refer to the figure
s 4.1 and 4.2 to make sure the
required airflow and the right position is used.
The dimensions of the sub rack are shown in fig 1.1
–
fig. 1.7
The terminal for input and output connection is at the rear side of the sub rack. The cable entry can be
made from rear or from bottom side. (see fig. 1.1
–
1.7)
For mounting the sub rack into your mains rack, you have to remove all the ups modules and the battery
treys from the sub rack.
Please use only the slides and brackets from the delivered accessories kit (see fig. 3.1
–
3.5)
Please follow the instruction drawing on fig. 2.1
–
2.7.
Note: for assembling the sub rack at a 19” rack you have to remove the UPS modules and the battery
shelves, while you need access for screw position (see Detail 12 on figure 2.1
–
2.7)
1.5.3.1
Table of Weight
UPScale RI
max. configuration
RI 10
RI 11
RI 12
RI 20
RI 22
RI 24
RI 40
Weight of empty frame
w/o modules and
w/o batteries
kg
20
40
56
25
66
93
50
Weight of empty frame
with modules and
w/o batteries
kg
39 - 42
59 - 62
75 - 78
44 - 47
104 -
110
131 -
137
124 -
136
Weight of empty frame
with modules and
with all batteries
kg
-
161 - 164
279 -
282
--
308 -
314
539 -
545
-
12V 7Ah battery block
2.5 kg
12V 9Ah battery block
2.55kg
UPS module M10
18.6 kg
UPS module M20
21.5 kg
Summary of Contents for DPA Upscale RI Series
Page 27: ......
Page 28: ......
Page 29: ......
Page 31: ......
Page 32: ......
Page 33: ......
Page 35: ......
Page 36: ......
Page 37: ......
Page 39: ......
Page 40: ......
Page 41: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 47: ......
Page 48: ......
Page 49: ......
Page 51: ......
Page 52: ......
Page 53: ......