10.12 WIRING AND BLOCK DIAGRAMS FOR ALL FRAMES AND MODULES
The customer has to supply the wiring to connect the UPS to the local power source. The installation inspection
and initial start up of the UPS and extra battery cabinet must be carried out by a qualified service personnel such
as a licensed service engineer from the manufacturer or from an agent certified by the manufacturer.
More details and procedure are mentioned in the user manual.
10.12.1 TERMINAL CONNECTIONS OVERVIEW
FRAME TYPE
Terminals (T)
Connection Bar (B)
Battery Earth
PE
Separate. Battery
(+ / N / - )
Common
Battery
(+ / N / - )
Input Bypass
3+N
Input Rectifier
3+N+PE
Output load
3+N+PE
UPScale RI 10
16/25mm
2
(T)
3 x 10/16mm
2
(T)
n.a
4 x 10/16 mm
2
(T)
5 x 10/16 mm
2
(T)
5 x 10/16 mm
2
(T)
UPScale RI 11
n.a.
n.a.
n.a.
UPScale RI 12
n.a.
n.a.
n.a.
UPScale RI20
16/25mm
2
(T)
2x
(3 x 10/16mm
2
) (T)
3 x M5 (B)
4 x 16/25 mm
2
(T)
5 x 16/25 mm
2
(T)
5 x 16/25 mm
2
(T)
UPScale RI 22
n.a.
n.a.
n.a.
UPScale RI 24
n.a.
n.a.
n.a.
UPScale RI40
50 mm
2
(T)
4x
(3 x 10/16mm
2
) (T)
3 x M6 (B)
3 x 50 mm
2
(T)
+ N 70/95 mm
2
(T)
3 x 50 mm
2
(T)
+ N 70/95 mm
2
(T)
+PE 50 mm
2
(T)
3 x 50 mm
2
(T)
+ N 70/95 mm
2
(T)
+PE 50 mm
2
(T)
n.a. = not allowed
UPScale RI 11, RI 12, RI 22, RI 24
(on rear site)
UPScale RI 10 (on rear site)
UPScale RI 20 (on rear site)
UPScale RI 40 (on rear site)
Batt.
Input
Output
Batt.
Input
Output
Batt.
Input
Output
Input
Output
Summary of Contents for DPA Upscale RI Series
Page 27: ......
Page 28: ......
Page 29: ......
Page 31: ......
Page 32: ......
Page 33: ......
Page 35: ......
Page 36: ......
Page 37: ......
Page 39: ......
Page 40: ......
Page 41: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 47: ......
Page 48: ......
Page 49: ......
Page 51: ......
Page 52: ......
Page 53: ......