Step
Action
4.
J3
-
Input Alarm Connection:
Insert the terminated end of the Alarm Input wireset (CC848817651or similar)
into the Input Alarms connector.
5.
J4
-
Output Alarm Connection:
Insert the terminated end of the Office Alarm Output wireset (CC848817635
or similar) into the Office Alarm connector on the top edge of the controller.
Configure alarm relays to
“
Open
”
or
“
Close
”
on alarm as required
:
These jumpers set the ten Form
-
C alarm outputs on the connector
J4
. Carefully move each of respective
configuration jumpers to the desired contact type:
“
Open On Alarm
”
or
“
Closed On Alarm
”
position as
required per site instructions.
Pin 1
6.
J5
-
Local Area Network (LAN) Connection:
Insert a 10/100Base
-
T CAT
-
5 LAN wireset into the LAN
connector on the top edge of the controller.
7.
Open the door to the widest position.
8.
Dress the field wiring using the tie points next to the upper hinge and out the side of the cabinet.
9.
Check to make sure the door can open and close without straining the connectors.