Status LEDs
The controller has LED indicators for more specific information on AC, DC and Battery on Discharge
states. These LEDs have factory assigned defaults as indicated in the table below. However, the
assignments to alarms can be customized in the field using the remote interfaces
Audible Alarm
LED
Status
Condition
AC
AC input to all rectifiers is in range.
AC input to one rectifier is missing or out of range.
AC input to two or more rectifiers is missing or out of range.
DC
DC output to all loads is normal.
One or more of the following alarms are present: Fuse Minor
One or more of the following alarms are present: Open
String, LVBD Open, Fuse Major
BD
System above configured Battery on Discharge (BD) threshold.
Blinks at an On/Off Rate of 1/2 second ON 1/4 second Off
to indicate a manual or automatic battery test in progress.
State not presently assigned.
System equal to or below configured Battery on Discharge (BD) threshold.
The Pulsar NE843 has an integrated audible alarm located in its display assembly. This alarm will sound
when any Critical, Major, or Minor alarm is detected by the controller. Upon assertion of the audible alarm
the default front panel will provide and indicator of the alarm as well as a quick link to temporary cut
-
off
the alarm.
Pressing the arrow key provides a quick link to temporarily cut
-
off the audible alarm.