Page 52
© Copyright 2021 ABB. All rights reserved.
Appendix C: Operation without a Controller
-
Alarm Wiring
Each converter shelf provides alarm contact closures for Power Major and Power Minor independently
of a controller. Wire these relays into the alarm network in deployments where a controller is not
utilized. When a controller is installed then an alarm cable can be attached to the controller –
see the
Connect Office Alarms section.
Converter Shelf Alarm Card State Table
This section shows Alarm and LED response for the Alarm Card LEDs and Relays:
The Converter Shelf contains a pair of A bus feeds and a pair of B bus feeds. The use of dual A and B
feeds is to not exceed the 48 AMPS L2 input current per feed. The A bus feeds are designated A1
-
6 and
A9
-
12, and power shelf slots 1
-
6 (left side) and 7
-
12 (right side) respectively. The B bus feeds are also
designated in an identical fashion. The alarm card monitors the
-
48v on each of these four feeds, and
asserts alarms and indicators
-
Table 11.
A
1
-
6
B
1
-
6
A
7
-
12
B
7
-
12
PMN
PMJ
1
OK
OK
OK
OK
GRN
GRN
GRN
OFF
2
LOW
OK
OK
OK
RED
GRN
OFF
YEL
3
OK
LOW
OK
OK
GRN
RED
OFF
YEL
4
OK
OK
LOW
OK
RED
GRN
OFF
YEL
5
OK
OK
OK
LOW
GRN
RED
OFF
YEL
6
LOW
LOW
OK
OK
RED
RED
OFF
RED
7
LOW
OK
LOW
OK
RED
GRN
OFF
RED
8
LOW
OK
OK
LOW
RED
RED
OFF
RED
9
OK
LOW
LOW
OK
RED
RED
OFF
RED
10
OK
LOW
OK
LOW
GRN
RED
OFF
RED
11
OK
OK
LOW
LOW
RED
RED
OFF
RED
12
LOW
LOW
LOW
OK
RED
RED
OFF
RED
13
LOW
LOW
OK
LOW
RED
RED
OFF
RED
14
LOW
OK
LOW
LOW
RED
RED
OFF
RED
15
OK
LOW
LOW
LOW
RED
RED
OFF
RED
16
LOW
LOW
LOW
LOW
OFF
OFF
OFF
OFF
Step
Action
designated.
6
5
4
3
2
1
TB1
Alarm Board
Open on Alarm
Open on Alarm
Open on Alarm
Open on Alarm
Return
Return
PMN
PMJ
Summary of Contents for CPS2400U
Page 2: ...Page 2 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 8: ...Page 8 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 12: ...Page 12 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 30: ...Page 30 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 49: ...Page 49 Copyright 2021 ABB All rights reserved Figure 33 Converter Slot Fillers ...