Page 33
© Copyright 2021 ABB. All rights reserved.
Alarm Card
The Alarm Card aggregates alarms from shelf Converter Cards, shelf
-
48V dc input feeds, and Fan
Shelves connected to its P2 connector. Alarm Card LEDs and Relays present the aggregated Alarm Card
State
-
Table 3.
Alarm Card LEDs and Relays
•
A
and
B
LEDs indicate the alarm state of each of the
-
48V Input Feeds to the shelf (see
Table 2
).
•
OK
and
ALM
LEDs and
Relays
indicate the combined alarm state of the shelf, including Converter Cards and
-
48V
input voltage feeds.
State
A
1
-
6
B
1
-
6
A
7
-
12
B
7
-
12
B
Green
Green
OK
Low
Red
Green
Minor
Low
Green
Red
Minor
Low
Red
Green
Minor
Low
Green
Red
Minor
Low
Low
Red
Red
Major
Low
Low
Red
Green
Major
Low
Low
Red
Red
Major
Low
Low
Red
Red
Major
Low
Low
Green
Red
Major
Low
Low
Red
Red
Major
Low
Low
Low
Red
Red
Major
Low
Low
Low
Red
Red
Major
Low
Low
Low
Red
Red
Major
Low
Low
Low
Red
Red
Major
Low
Low
Low
Low
Unpowered
Alarm State LEDs
OK and ALM
Input Feed
LEDs A and B
5 Empty cells indicate: OK for inputs, OFF for LEDs, and non
-
alarm for relays.
Summary of Contents for CPS2400U
Page 2: ...Page 2 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 8: ...Page 8 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 12: ...Page 12 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 30: ...Page 30 Copyright 2021 ABB All rights reserved This page intentionally left blank Jl ll ll ...
Page 49: ...Page 49 Copyright 2021 ABB All rights reserved Figure 33 Converter Slot Fillers ...