186 Parameters
(Visible when
Defines the real value of the signal (selected by parameter
) that corresponds to the maximum AO2
output value (defined by parameter
.
100.0
-32768.0 …
32767.0
Real signal value corresponding to maximum AO2 output
value.
1 = 1
(Visible when
Defines the minimum output value for analog output AO2.
See also drawing at parameter
0.000 mA
0.000 … 22.000 mA Minimum AO2 output value.
1000 = 1 mA
(Visible when
Defines the maximum output value for analog output AO2.
See also drawing at parameter
10.000 mA
0.000 … 22.000 mA Maximum AO2 output value.
1000 = 1 mA
15
Configuration of I/O extension module 2.
See also section
(page
Note:
The contents of the parameter group vary according to
the selected I/O extension module type.
See parameter
.
See parameter
.
See parameter
(Visible when
)
See parameter
-
(Visible when
)
See parameter
.
-
(Visible when
)
See parameter
-
(Visible when
)
See parameter
-
(Visible when
)
See parameter
.
10.0 ms
(Visible when
)
See parameter
10.0 ms
(Visible when
)
See parameter
(Visible when
)
See parameter
.
(Visible when
)
See parameter
.
0.00 s
(Visible when
)
See parameter
0.00 s
(Visible when
)
See parameter
.
0.00 s
(Visible when
)
See parameter
0.00 s
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...