168 Parameters
Slot 3
Slot 3.
3
4…254
Node ID of the slot on the FEA-03 extension adapter.
1 = 1
Displays the status of I/O extension module 1.
No option
No module detected in the specified slot.
0
No communication
A module has been detected but cannot be communicated
with.
1
Unknown
The module type is unknown.
2
FIO-01
An FIO-01 module has been detected and is active.
15
FIO-11
An FIO-11 module has been detected and is active.
20
FAIO-01
An FAIO-01 module has been detected and is active.
24
(Visible when
)
Displays the status of the digital inputs on the extension
module. The activation/deactivation delays (if any are
specified) are ignored. A filtering time (for input mode) can be
defined by parameter
.
Bit 0 indicates the status of DI1.
Note:
The number of active bits in this parameter depends on
the number of digital input/outputs on the extension module.
Example:
0101b = DI1 and DI3 are on, remainder are off.
This parameter is read-only.
-
0000b…1111b
Status of digital inputs.
1 = 1
(Visible when
)
Displays the status of the digital input/outputs on the
extension module. The activation/deactivation delays (if any
are specified) are ignored. A filtering time (for input mode) can
be defined by parameter
.
Bit 0 indicates the status of DIO1.
Note:
The number of active bits in this parameter depends on
the number of digital input/outputs on the extension module.
Example:
1001b = DIO1 and DIO4 are on, remainder are off.
This parameter is read-only.
-
0000b…1111b
Status of digital input/outputs.
1 = 1
(Visible when
)
Displays the delayed status of the digital inputs on the
extension module. The word is updated only after
activation/deactivation delays (if any are specified).
Bit 0 indicates the status of DI1.
Note:
The number of active bits in this parameter depends on
the number of digital inputs on the extension module.
Example:
0101b = DI1 and DI3 are on, remainder are off.
This parameter is read-only.
-
0000b…1111b
Delayed status of digital inputs.
1 = 1
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS880-x04
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Page 4: ......
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 112: ...112 Application macros ...
Page 496: ...496 Additional parameter data ...
Page 544: ...544 Fault tracing ...
Page 602: ...602 Control chain diagrams ...