8 Quick start-up guide
the brake control function), but it has to be implemented as defined in the application
specific regulations.
Centrifuge drive start-up
The checklist for Centrifuge drive start-up is given below:
Step
Action
1
Connect digital and analog I/Os according to the wiring diagram shown in section
Centrifuge I/O control connections
2
Perform basic start-up of the drive. See
ACS880 primary control program firmware
manual (3AUA0000085967[English])
.
3
Activate Centrifuge control program with parameter
.
4
Activate default relay outputs and default actual values on the control panel with
parameters 10.24...10.32. See
ACS880 primary control program firmware manual
(3AUA0000085967[English]).
5
Set speed limits with following parameters:
•
•
•
•
•
6
Set acceleration and deceleration ramps with following parameters:
•
and
•
7
Tune other parameters required for controlling the Centrifuge sequence. See parameter
group
.
8
The drive is ready to run.
Perform a test run with the motors de-coupled in the driven machinery. Start the drive
locally by following the instructions in section