Parameters 247
Stall current limit in percent of the nominal current of the
motor. See parameter
.
200.0%
0.0…1600.0%
Stall current limit.
-
Stall speed limit in rpm. See parameter
150.00 rpm;
180.00 rpm
(
b0)
0.00…10000.00 rpm
Stall speed limit.
See par.
Stall frequency limit. See parameter
Note: Setting the limit below 10 Hz is not recommended.
15.00 Hz;
18.00 Hz
(
b0)
0.00…500.00 Hz
Stall frequency limit.
See par.
.
20 s
0…3600 s
Stall time.
-
Defines, together with
, the maximum allowed speed of the
motor (overspeed protection). If actual speed (
) exceeds the speed limit defined by
by more than the value of this
parameter, the drive trips on the
fault.
WARNING! This function only supervises the
speed in DTC motor control mode. The function is
not effective in scalar motor control mode.
Example: If the maximum speed is 1420 rpm and speed
trip margin is 300 rpm, the drive trips at 1720 rpm.
500.00 rpm
0.00…10000.0 rpm
Overspeed trip margin.
See par.
No.
Name/Value
Description
Def/
FbEq16
Speed (
Time
Overspeed trip level
Overspeed trip level
0
Summary of Contents for ACS880 PCP
Page 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Page 4: ......
Page 28: ...28 PCP ESP control start up ...
Page 30: ...30 Using the control panel ...
Page 94: ...94 Standard programposi features ...
Page 100: ...100 Default control connections ...
Page 360: ...360 Parameters ...
Page 436: ...436 Fault tracing ...
Page 486: ...486 Control chain diagrams ...
Page 492: ...492 Appendix ESP with step up transformer and sine filter ...
Page 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...