280 Parameters
Source selection (see
on
page
-
Specifies the currency used for the savings calculations.
Local currency
Local currency. The name of the currency can be edited by
choosing Menu - Settings - Edit texts on the control panel.
100
EUR
Euro.
101
USD
US dollar.
102
Defines a factor for conversion of saved energy into CO
2
emissions (kg/kWh or tn/MWh).
0.500 tn/MWh
0.000
…65.535 tn/MWh
Factor for conversion of saved energy into CO
2
emissions. 1 = 1 tn/MWh
Actual power that the motor absorbs when connected
direct-on-line and operating the application. The value is
used for reference when energy savings are calculated.
Note: The accuracy of the energy savings calculation is
directly dependent on the accuracy of this value. If nothing
is entered here, then the nominal motor power is used by
the calculation, but that may inflate the energy savings
reported as many motors do not absorb nameplate power.
0.0 kW
0.0…100000.0 kW
Motor power.
See par.
46.04
Resets the savings counter parameters
Done
Reset not requested (normal operation), or reset complete. 0
Reset
Reset the savings counter parameters. The value reverts
automatically to
1
46
Speed supervision settings; actual signal filtering; general
scaling settings.
Defines the maximum speed value used to define the
acceleration ramp rate and the initial speed value used to
define the deceleration ramp rate (see parameter group
). The speed acceleration and
deceleration ramp times are therefore related to this value
(not to parameter
Also defines the 16-bit scaling of speed-related
parameters. The value of this parameter corresponds to
20000 in fieldbus, master/follower etc. communication.
1500.00 rpm;
1800.00 rpm
(
b0)
0.10…30000.00 rpm
Acceleration/deceleration terminal/initial speed.
1 = 1 rpm
Defines the maximum frequency value used to define the
acceleration ramp rate and the initial frequency value used
to define deceleration ramp rate (see parameter group
). The frequency acceleration
and deceleration ramp times are therefore related to this
value (not to parameter
Also defines the 16-bit scaling of frequency-related
parameters. The value of this parameter corresponds to
20000 in fieldbus, master/follower etc. communication.
50.00 Hz;
60.00 Hz
(
b0)
0.10…1000.00 Hz
Acceleration/deceleration terminal/initial frequency.
10 = 1 Hz
No.
Name/Value
Description
Def/
FbEq16
Summary of Contents for ACS880 PCP
Page 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Page 4: ......
Page 28: ...28 PCP ESP control start up ...
Page 30: ...30 Using the control panel ...
Page 94: ...94 Standard programposi features ...
Page 100: ...100 Default control connections ...
Page 360: ...360 Parameters ...
Page 436: ...436 Fault tracing ...
Page 486: ...486 Control chain diagrams ...
Page 492: ...492 Appendix ESP with step up transformer and sine filter ...
Page 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...