The settings of the FSO module have default values when delivered from the factory. The
wiring of the external safety circuit and configuration of the FSO module are the responsibility
of the user.
The FSO module reserves the standard Safe torque off (STO) connection of the drive control
unit. STO can still be utilized by other safety circuits through the FSO module.
See the appropriate manual for more information.
Code
Name
FSO-12 safety functions module user's manual
FSO-21 safety functions module user's manual
Implementing the power loss ride-through function
If the incoming supply voltage is cut off, the drive will continue to operate by utilizing the
kinetic energy of the rotating motor. The drive will be fully operational as long as the motor
rotates and generates energy to the drive.
If the drive is equipped with a main contactor or breaker, it restores the drive input power
after a short break. The contactor re-connects after the break automatically. If the drive is
equipped an external uninterruptible auxiliary power supply (G307), it keeps the
main contactor closed in power-loss situations
Note:
If the power loss lasts so long that the drive trips on undervoltage, a fault reset and
a fresh start command is required to continue operation.
Implement the power-loss ride-through function as follows:
1.
Enable the power-loss ride-through function of the drive (parameter
30.31
).
2.
Enable the automatic restart of the motor after a short power supply break:
•
Set the start mode to automatic (parameter
21.01
or
21.19
, depending on the motor
control mode being used).
•
Define the automatic restart time (parameter
21.18
).
WARNING!
Make sure that a flying restart of the motor will not cause any danger. If you are in
doubt, do not implement the power loss ride-through function.
Implementing a bypass connection
If bypassing is required, employ mechanically or electrically interlocked contactors between
the motor and the drive and between the motor and the power line. Make sure with
interlocking that the contactors cannot be closed simultaneously. The installation must be
clearly marked as defined in IEC/EN/UL 61800-5-1, subclause 6.5.3, for example, “THIS
MACHINE STARTS AUTOMATICALLY”.
Bypass connection is available as a factory-installed option for some cabinet-installed drive
types. Consult ABB for more information.
WARNING!
Never connect the drive output to the electrical power network. The connection may
damage the drive.
88 Guidelines for planning the electrical installation
Summary of Contents for ACS880-37LC-0390A-7
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 37LC drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 13: ...16 Resistor braking Further information Table of contents 13 ...
Page 14: ...14 ...
Page 24: ...24 ...
Page 28: ...28 ...
Page 50: ...50 ...
Page 70: ...70 Mechanical installation ...
Page 110: ...10 110 Electrical installation ...
Page 113: ...With FDPI 02 modules OPEN TERMINATED 1 1 2 2 OPEN TERMINATED 3 Electrical installation 113 11 ...
Page 134: ...134 ...
Page 140: ...140 ...
Page 148: ...a b c 148 Maintenance ...
Page 151: ...4 5 6 Maintenance 151 ...
Page 164: ...164 ...
Page 174: ...174 ...
Page 196: ...196 ...
Page 199: ... Dimension drawing examples ACS880 37LC 0390A 7 with main contactor Dimensions 199 ...
Page 201: ...ACS880 37LC 1270A 7 with common motor terminal cubicle Dimensions 201 ...
Page 202: ...ACS880 37LC 1940A 7 with common motor terminal cubicle 202 Dimensions ...
Page 205: ...Location and size of input terminals Contact ABB for details Dimensions 205 ...
Page 206: ... 100 kA input cubicle option F274 206 Dimensions ...
Page 208: ...Inverter module cubicle with two R8i modules bottom cable exit 208 Dimensions ...
Page 209: ...Inverter module cubicle with three R8i modules bottom cable exit Dimensions 209 ...
Page 210: ...Brake chopper cubicle 210 Dimensions ...
Page 212: ...Cubicle width 300 mm top cable exit 212 Dimensions ...
Page 213: ...Cubicle width 400 mm bottom cable exit Dimensions 213 ...
Page 214: ...Cubicle width 400 mm top cable exit 214 Dimensions ...
Page 215: ...Cubicle width 600 mm bottom cable exit Dimensions 215 ...
Page 216: ...Cubicle width 600 mm top cable exit 216 Dimensions ...
Page 238: ...238 ...
Page 240: ...240 ...