cross-sectional area of the protective earth conductor must be determined in a manner
which produces a conductance equivalent to that which results from the application of this
table.
Minimum cross-sectional area of the corresponding
protective earth conductor
S
p
(mm
2
)
Cross-sectional area of the phase conductors
S (mm
2
)
S
1)
S ≤ 16
16
16 < S ≤ 35
S/2
35 < S
1) For the minimum conductor size in IEC installations, refer to
Additional grounding requirements – IEC
.
If the protective earth conductor is not part of the input power cable or input power cable
enclosure, the minimum permitted cross-sectional area is:
•
2.5 mm
2
if the conductor is mechanically protected,
or
•
4 mm
2
if the conductor is not mechanically protected. If the equipment is cord-connected,
the protective earth conductor must be the last conductor to be interrupted if there is a
failure in the strain relief mechanism.
■
Additional grounding requirements – IEC
This section gives grounding requirements according to standard IEC/EN 61800-5-1.
Because the normal touch current of the drive is more than 3.5 mA AC or 10 mA DC:
•
the minimum size of the protective earth conductor must comply with the local safety
regulations for high protective earth conductor current equipment, and
•
you must use one of these connection methods:
1.
a fixed connection and:
•
a protective earth conductor with a minimum cross-sectional area of 10 mm
2
Cu or 16 mm
2
Al (as an alternative when aluminum cables are permitted),
or
•
a second protective earth conductor of the same cross-sectional area as the
original protective earth conductor,
or
•
a device that automatically disconnects the supply if the protective earth
conductor is damaged.
2.
a connection with an industrial connector according to IEC 60309 and a minimum
protective earth conductor cross-section of 2.5 mm
2
as part of a multi-conductor
power cable. Sufficient strain relief must be provided.
If the protective earth conductor is routed through a plug and socket, or similar means of
disconnection, it must not be possible to disconnect it unless power is simultaneously
removed.
Note:
You can use power cable shields as grounding conductors only when their conductivity
is sufficient.
■
Additional grounding requirements – UL (NEC)
This section gives grounding requirements according to standard UL 61800-5-1.
82 Guidelines for planning the electrical installation
Summary of Contents for ACS880-37LC-0390A-7
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 37LC drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 13: ...16 Resistor braking Further information Table of contents 13 ...
Page 14: ...14 ...
Page 24: ...24 ...
Page 28: ...28 ...
Page 50: ...50 ...
Page 70: ...70 Mechanical installation ...
Page 110: ...10 110 Electrical installation ...
Page 113: ...With FDPI 02 modules OPEN TERMINATED 1 1 2 2 OPEN TERMINATED 3 Electrical installation 113 11 ...
Page 134: ...134 ...
Page 140: ...140 ...
Page 148: ...a b c 148 Maintenance ...
Page 151: ...4 5 6 Maintenance 151 ...
Page 164: ...164 ...
Page 174: ...174 ...
Page 196: ...196 ...
Page 199: ... Dimension drawing examples ACS880 37LC 0390A 7 with main contactor Dimensions 199 ...
Page 201: ...ACS880 37LC 1270A 7 with common motor terminal cubicle Dimensions 201 ...
Page 202: ...ACS880 37LC 1940A 7 with common motor terminal cubicle 202 Dimensions ...
Page 205: ...Location and size of input terminals Contact ABB for details Dimensions 205 ...
Page 206: ... 100 kA input cubicle option F274 206 Dimensions ...
Page 208: ...Inverter module cubicle with two R8i modules bottom cable exit 208 Dimensions ...
Page 209: ...Inverter module cubicle with three R8i modules bottom cable exit Dimensions 209 ...
Page 210: ...Brake chopper cubicle 210 Dimensions ...
Page 212: ...Cubicle width 300 mm top cable exit 212 Dimensions ...
Page 213: ...Cubicle width 400 mm bottom cable exit Dimensions 213 ...
Page 214: ...Cubicle width 400 mm top cable exit 214 Dimensions ...
Page 215: ...Cubicle width 600 mm bottom cable exit Dimensions 215 ...
Page 216: ...Cubicle width 600 mm top cable exit 216 Dimensions ...
Page 238: ...238 ...
Page 240: ...240 ...