Guidelines for planning the electrical
installation
Contents of this chapter
This chapter contains instructions for planning the electrical installation of the drive. Some
instructions are mandatory to follow in every installation, others provide useful information
that only concerns certain applications.
Limitation of liability
The installation must always be designed and made according to applicable local laws and
regulations. ABB does not assume any liability whatsoever for any installation which breaches
the local laws and/or other regulations. Furthermore, if the recommendations given by ABB
are not followed, the drive may experience problems that the warranty does not cover.
Selecting the supply disconnecting device
The drive is equipped with a main disconnecting device as standard. Depending on the size
of the drive, and the selected options, the type of disconnecting device may vary. Examples:
switch-disconnector, withdrawable air circuit breaker, etc.
Selecting the main breaker option
The drive is equipped with an air circuit breaker in the incoming cubicle as standard (+F255).
Optionally, the drive may be ordered without an air circuit breaker (+F255
disabled/deselected). In this case, the supply panel of the drive must be equipped with a
main breaker. The control interface for this external breaker is located in the drive’s input
cubicle.
5
Guidelines for planning the electrical installation 73
Summary of Contents for ACS880-37LC-0390A-7
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 37LC drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 13: ...16 Resistor braking Further information Table of contents 13 ...
Page 14: ...14 ...
Page 24: ...24 ...
Page 28: ...28 ...
Page 50: ...50 ...
Page 70: ...70 Mechanical installation ...
Page 110: ...10 110 Electrical installation ...
Page 113: ...With FDPI 02 modules OPEN TERMINATED 1 1 2 2 OPEN TERMINATED 3 Electrical installation 113 11 ...
Page 134: ...134 ...
Page 140: ...140 ...
Page 148: ...a b c 148 Maintenance ...
Page 151: ...4 5 6 Maintenance 151 ...
Page 164: ...164 ...
Page 174: ...174 ...
Page 196: ...196 ...
Page 199: ... Dimension drawing examples ACS880 37LC 0390A 7 with main contactor Dimensions 199 ...
Page 201: ...ACS880 37LC 1270A 7 with common motor terminal cubicle Dimensions 201 ...
Page 202: ...ACS880 37LC 1940A 7 with common motor terminal cubicle 202 Dimensions ...
Page 205: ...Location and size of input terminals Contact ABB for details Dimensions 205 ...
Page 206: ... 100 kA input cubicle option F274 206 Dimensions ...
Page 208: ...Inverter module cubicle with two R8i modules bottom cable exit 208 Dimensions ...
Page 209: ...Inverter module cubicle with three R8i modules bottom cable exit Dimensions 209 ...
Page 210: ...Brake chopper cubicle 210 Dimensions ...
Page 212: ...Cubicle width 300 mm top cable exit 212 Dimensions ...
Page 213: ...Cubicle width 400 mm bottom cable exit Dimensions 213 ...
Page 214: ...Cubicle width 400 mm top cable exit 214 Dimensions ...
Page 215: ...Cubicle width 600 mm bottom cable exit Dimensions 215 ...
Page 216: ...Cubicle width 600 mm top cable exit 216 Dimensions ...
Page 238: ...238 ...
Page 240: ...240 ...