Default I/O diagram of the supply control unit
The diagram below shows the default I/O connections on the supply control unit (A51), and
describes the use of the connections in the supply unit. Under normal circumstances, the
factory-made wiring should not be changed.
The wire size accepted by all screw terminals (for both stranded and solid wire) is
0.5 … 2.5 mm
2
(22 … 12 AWG). The tightening torque is 0.45 N·m (4 lbf·in).
Description
Terminal
Drive-to-drive link
XD2D
Not in use by default
B
1
1
2
3
4
A
2
BGND
3
Shield
4
Drive-to-drive link termination switch
1)
D2D.TERM
ON
OFF
RS485 connection
X485
Cooling fan monitoring (CIO module)
B
5
5
6
7
8
A
6
BGND
7
Shield
8
Relay outputs
XRO1, XRO2, XRO3
XRO1:
Charging
2)
(Energized = Closes
charging contactor.)
250 V AC / 30 V DC, 2 A
Norm. closed
NC
11
22
23
31
32
11
12
13
21
33
Common
COM
12
Norm. open
NO
13
XRO2:
Fault (-1)
3)
(Energized = Indicates
no fault.)
250 V AC / 30 V DC, 2 A
Norm. closed
NC
21
Common
COM
22
Norm. open
NO
23
XRO3:
MCB ctrl
2)
(Energized = Closes
main contactor/breaker.)
250 V AC / 30 V DC, 2 A
Norm. closed
NC
31
Common
COM
32
Norm. open
NO
33
Safe torque off
4)
XSTO, XSTO OUT
XSTO: Factory connection. Both circuits (power module, control unit) must be
closed for the supply unit to start (IN1 and IN2 must be connected to OUT).
OUT
1
5
6
7
8
1
2
3
4
SGND
2
IN1
3
IN2
4
XSTO OUT: Not in use.
IN1
5
SGND
6
IN2
7
SGND
8
Digital inputs
XDI
120 Control units of the drive
Summary of Contents for ACS880-37LC-0390A-7
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 37LC drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 13: ...16 Resistor braking Further information Table of contents 13 ...
Page 14: ...14 ...
Page 24: ...24 ...
Page 28: ...28 ...
Page 50: ...50 ...
Page 70: ...70 Mechanical installation ...
Page 110: ...10 110 Electrical installation ...
Page 113: ...With FDPI 02 modules OPEN TERMINATED 1 1 2 2 OPEN TERMINATED 3 Electrical installation 113 11 ...
Page 134: ...134 ...
Page 140: ...140 ...
Page 148: ...a b c 148 Maintenance ...
Page 151: ...4 5 6 Maintenance 151 ...
Page 164: ...164 ...
Page 174: ...174 ...
Page 196: ...196 ...
Page 199: ... Dimension drawing examples ACS880 37LC 0390A 7 with main contactor Dimensions 199 ...
Page 201: ...ACS880 37LC 1270A 7 with common motor terminal cubicle Dimensions 201 ...
Page 202: ...ACS880 37LC 1940A 7 with common motor terminal cubicle 202 Dimensions ...
Page 205: ...Location and size of input terminals Contact ABB for details Dimensions 205 ...
Page 206: ... 100 kA input cubicle option F274 206 Dimensions ...
Page 208: ...Inverter module cubicle with two R8i modules bottom cable exit 208 Dimensions ...
Page 209: ...Inverter module cubicle with three R8i modules bottom cable exit Dimensions 209 ...
Page 210: ...Brake chopper cubicle 210 Dimensions ...
Page 212: ...Cubicle width 300 mm top cable exit 212 Dimensions ...
Page 213: ...Cubicle width 400 mm bottom cable exit Dimensions 213 ...
Page 214: ...Cubicle width 400 mm top cable exit 214 Dimensions ...
Page 215: ...Cubicle width 600 mm bottom cable exit Dimensions 215 ...
Page 216: ...Cubicle width 600 mm top cable exit 216 Dimensions ...
Page 238: ...238 ...
Page 240: ...240 ...