Guidelines for planning the electrical installation 59
Protecting the motor insulation and bearings
The drive uses modern IGBT inverter technology. Regardless of frequency, the drive
output has pulses of approximately the drive DC bus voltage with a very short rise time. Up
to twice bus voltage can be at the motor terminals, depending on the attenuation and
reflection properties of the motor cable and the terminals. The increased voltage can
cause additional stress on the motor and motor cable insulation.
Modern variable speed drives with their fast rising voltage pulses and high switching
frequencies can generate current pulses that flow through the motor bearings. This can
gradually erode the bearing races and rolling elements.
Optional d
u
/d
t
filters protect motor insulation system and reduce bearing currents.
Optional common mode filters mainly reduce bearing currents. Insulated N-end (non-drive
end) bearings protect the motor bearings.
Requirements table
The following table shows how to select the motor insulation system and when optional
ABB d
u
/d
t
filters, insulated N-end (non-drive end) motor bearings and ABB common mode
filters are required. Failure of the motor to fulfill the following requirements or improper
installation may shorten motor life or damage the motor bearings and voids the motor
warranty.
Motor
type
Nominal AC supply
voltage
Requirement for
Motor
insulation
system
ABB d
u
/d
t
and common mode filters, insulated N-end
motor bearings
100 kW <
P
N
<
350 kW
or
IEC 315 < frame size <
IEC 400
P
N
>
350 kW
or
frame size > IEC 400
134 hp <
P
N
<
469 hp
or
NEMA 500 < frame size <
NEMA 580
P
N
>
469 hp
or
frame size >
NEMA 580
ABB motors
Random
-wound
M2_,
M3_ and
M4_
U
N
< 500 V
Standard
+ N
+ N + CMF
500 V <
U
N
< 600 V
Standard
+ N + d
u
/d
t
+ N + d
u
/d
t
+ CMF
or
Reinforced
+ N
+ N + CMF
600 V <
U
N
< 690 V
(cable length < 150 m)
Reinforced
+ N + d
u
/d
t
+ N + d
u
/d
t
+ CMF
600 V <
U
N
< 690 V
(cable length > 150 m)
Reinforced
+ N
+ N + CMF
Form-
wound
HX_ and
AM_
380 V <
U
N
< 690 V
Standard
+ N + CMF
P
N
<
500 kW:
+N + CMF
P
N
>
500 kW
+N + d
u
/d
t
+ CMF
Old*
form-
wound
HX_ and
modular
380 V <
U
N
< 690 V
Check with
the motor
manufacturer.
+ N + d
u
/d
t
with voltages over 500 V + CMF
Summary of Contents for ACS880-34
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 34 drive modules 132 to 400 kW 200 to 450 hp Hardware manual ...
Page 4: ......
Page 14: ...14 ...
Page 22: ...22 Safety instructions ...
Page 28: ...28 Introduction to the manual ...
Page 42: ...42 Operation principle and hardware description ...
Page 118: ...118 External control unit ...
Page 140: ...140 Installation example with full cabling panels option H381 M8 16 Hex 2 5 4 3 1 1 1 1 2 6 7 ...
Page 152: ...152 Installation checklist ...
Page 156: ...156 Start up ...
Page 158: ...158 Fault tracing ...
Page 174: ...174 Maintenance ...
Page 202: ...202 Technical data EU Declaration of Conformity Machinery Directive ...
Page 204: ...204 Technical data ...
Page 206: ...206 Dimension drawings Standard configuration 3AXD50000038012 ...
Page 208: ...208 Dimension drawings Drive module with options 0B051 H356 0H371 3AXD50000038012 ...
Page 209: ...Dimension drawings 209 Configuration with option H381 3AXD50000323210 ...
Page 210: ...210 Dimension drawings LCL filter module 3AXD50000206162 ...
Page 214: ...214 Dimension drawings External control unit 3axd50000011687 ...
Page 238: ...238 Resistor braking ...
Page 242: ...242 du dt and sine filters ...
Page 256: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035191 Rev B EN 2018 09 28 ...