![ABB ACS880-34 Hardware Manual Download Page 193](http://html.mh-extra.com/html/abb/acs880-34/acs880-34_hardware-manual_2653193.webp)
Technical data 193
The cooling air temperature rises 30 degrees Celsius when it goes through the drive
module if the temperature of the input cooling air is 40 degrees Celsius.
Terminal and entry data for the power cables
The maximum accepted cable size is 4 × (3 × 240) mm
2
or 4 × (3 × 500 AWG). Screw size
for connecting busbars to the drive module input and output busbars: M12, tightening
torque 50...75 N·m.
Units with optional cabling panels (+H381)
The maximum accepted cable size is 4 × (3 × 240) mm
2
or 4 × (3 × 500 AWG). The
cabling panels are connected to the drive module busbars with M12 serpress nuts,
tightening torque 30 N·m (20 lbf·ft).
Input, motor and brake resistor cable terminal sizes and tightening torques are given
below.
Two-hole 1/2 inch diameter cable lugs can be used.
Units without full-size output cable connection terminals (+0H371)
and with a common mode filter (+E208)
It is possible to use the maximum cable size (4 × [3 × 240] mm2 or 4 ×[(3 × 500 AWG])
only with special cable lugs and additional insulation. For more information, contact your
local ABB representative.
Terminal data for the control cables
See page
or
.
ACS880-34-142A-7
R11
2100
1279
5 280
75
ACS880-34-174A-7
R11
2100
1279
6 400
75
ACS880-34-210A-7
R11
2100
1279
8 000
75
ACS880-34-271A-7
R11
2100
1279
10 000
75
ACS880-34-330A-7
R11
2100
1279
12 600
75
ACS880-34-370A-7
R11
2100
1279
14 200
75
ACS880-34-430A-7
R11
2100
1279
16 000
75
L1/U1, L2/V1, L3/W1, T1/U2, T2/V2, T3/W2, UDC+, UDC-
Grounding busbar
Screw
Tightening torque
Screw
Tightening torque
N-m
lbf·ft
N-m
lbf·ft
M12
1/2
50...75
37...55
M10
3/8
30...44
22...32
Electrical power network specification
Voltage (
U
1
)
ACS880-34-xxxx-3 drive modules: 380…415 V AC phase
+10%/-15%. This
is indicated in the type designation label as typical input voltage level
3
400 V AC.
ACS880-34-xxxx-5 drive modules: 380...500 V AC 3-phase
+10%/-15%. This
is indicated in the type designation label as typical input voltage levels
3
400/480/500 V AC.
ACS880-34-xxxx-7 drive modules: 525…690 V AC 3-phase
+10%/-15%. This
is indicated in the type designation label as typical input voltage levels
3
525/600/690 (600 UL, CSA) V AC .
Drive type
Frame size
Air flow
Heat dissipation
Noise
m
3
/h
ft
3
/min
W
dB(A)
~
~
~
Summary of Contents for ACS880-34
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 34 drive modules 132 to 400 kW 200 to 450 hp Hardware manual ...
Page 4: ......
Page 14: ...14 ...
Page 22: ...22 Safety instructions ...
Page 28: ...28 Introduction to the manual ...
Page 42: ...42 Operation principle and hardware description ...
Page 118: ...118 External control unit ...
Page 140: ...140 Installation example with full cabling panels option H381 M8 16 Hex 2 5 4 3 1 1 1 1 2 6 7 ...
Page 152: ...152 Installation checklist ...
Page 156: ...156 Start up ...
Page 158: ...158 Fault tracing ...
Page 174: ...174 Maintenance ...
Page 202: ...202 Technical data EU Declaration of Conformity Machinery Directive ...
Page 204: ...204 Technical data ...
Page 206: ...206 Dimension drawings Standard configuration 3AXD50000038012 ...
Page 208: ...208 Dimension drawings Drive module with options 0B051 H356 0H371 3AXD50000038012 ...
Page 209: ...Dimension drawings 209 Configuration with option H381 3AXD50000323210 ...
Page 210: ...210 Dimension drawings LCL filter module 3AXD50000206162 ...
Page 214: ...214 Dimension drawings External control unit 3axd50000011687 ...
Page 238: ...238 Resistor braking ...
Page 242: ...242 du dt and sine filters ...
Page 256: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035191 Rev B EN 2018 09 28 ...