Losses, cooling data and noise
Noise
Heat dissipation
Air flow
Frame
size
ACS880-
14-
W
ft
3
/min
m
3
/h
dB(A)
U
n
= 400 V
75
5280
1236
2100
R11
246A-3
75
6400
1236
2100
R11
293A-3
75
8000
1236
2100
R11
363A-3
75
10000
1236
2100
R11
442A-3
75
10000
1236
2100
R11
505A-3
75
12600
1236
2100
R11
585A-3
75
14200
1236
2100
R11
650A-3
U
n
= 500 V
75
5280
1236
2100
R11
240A-5
75
6400
1236
2100
R11
260A-5
75
8000
1236
2100
R11
302A-5
75
8000
1236
2100
R11
361A-5
75
10000
1236
2100
R11
414A-5
75
12600
1236
2100
R11
460A-5
75
14200
1236
2100
R11
503A-5
U
n
= 690 V
75
5280
1236
2100
R11
142A-7
75
6400
1236
2100
R11
174A-7
75
8000
1236
2100
R11
210A-7
75
10000
1236
2100
R11
271A-7
75
12600
1236
2100
R11
330A-7
75
14200
1236
2100
R11
370A-7
75
16000
1236
2100
R11
430A-7
These losses are not calculated according to IEC 61800-9-2.
Typical power cable sizes
US
2)
IEC
1)
Al cable type
Cu cable type
Al cable type
Cu cable type
ACS880-
14-…
AWG/kcmil
AWG/kcmil
mm
2
mm
2
U
n
= 400 V
350 MCM or 2 × 2/0
250 MCM or 2 × 1
2 × (3 × 95)
2 × (3 × 50)
246A-3
500 MCM or 2 × 3/0
350 MCM or 2 × 2/0
2 × (3 × 120)
2 × (3 × 70)
293A-3
700 MCM or 2 × 4/0 or 3 × 2/0
500 MCM or 2 × 3/0
3 × (3 × 95)
3 × (3 × 50)
363A-3
2 × 300 MCM or 3 × 3/0
700 MCM or 2 × 4/0 or 3 × 2/0
3 × (3 × 120)
3 × (3 × 70)
442A-3
2 × 300 MCM or 3 × 3/0
700 MCM or 2 × 4/0 or 3 × 2/0
3 × (3 × 120)
3 × (3 × 70)
505A-3
2 × 500 MCM or 3 × 250 MCM
2 × 350 MCM or 3 × 4/0
3 × (3 × 150)
3 × (3 × 120)
585A-3
2 × 600 MCM or 3 × 300 MCM
2 × 400 MCM or 3 × 4/0
3 × (3 × 185)
3 × (3 × 120)
650A-3
Technical data and references 281