Note:
The +H366 option only interconnects the outputs of inverter modules within the same
cubicle, not modules installed in different cubicles. Therefore, when the drive has more than
three inverter modules, make sure that the load is distributed evenly between the modules:
•
In case of two inverter cubicles of two modules, connect the same number of cables to
each cubicle.
•
In case of one inverter cubicle with three modules and another with two, each cubicle
requires a number of cables proportional to the number of modules within. For example,
connect three out of five (or six out of ten, etc.) cables to the cubicle with three modules,
the remaining two out of five (four out of ten) cables to the cubicle with two modules.
■
Procedure
Removing the inverter module(s)
To allow more room for cabling work, the inverter modules can be removed completely
instead of only the fan carriages.
Refer to the drawings below.
Note:
As an alternative to using the extraction/installation ramp, a lifter is available from
ABB Service. See
Lifter for air-cooled drive modules user's guide
(3AXD50000332588
[English]).
WARNING!
Read the safety instructions given in
Safety instructions for ACS880
multidrive cabinets and modules
(3AUA0000102301 [English]). If you
ignore them, injury or death, or damage to the equipment can occur.
Note:
The illustrations represent a frame 2×R8i inverter cubicle with F286 (DC
switch-disconnector). On units wF286, the DC busbars are oriented differently, but
the procedure is otherwise the same.
1.
Do the steps in section
Electrical safety precautions (page 57)
before you start the work.
2.
Open the inverter module cubicle door.
3.
Remove the shroud at the top of the cubicle.
4.
Detach the terminal block [X50] at the top of the module.
5.
Detach the DC busbars from the module. Make note of the order and position of the
screws and washers.
6.
Detach the wiring connected to the terminals on the front of the module (including fiber
optic cabling). Move the disconnected wiring aside.
7.
Drives with C121 (Marine construction) or +C180 (Seismic design):
a.
Loosen the bolts holding the transverse retaining bracket both on the left and the
right. (During reassembly, tighten these screws to 9 N·m [6.6 lbf·ft].)
b.
Remove the bolts holding the retaining bracket to the module.
c.
Remove the retaining bracket.
d.
Reinstall the bolts to the module. Tighten to 22 N·m (16 lbf·ft).
WARNING!
Do not proceed before the bolts are securely in place.
Otherwise, the parts of the module can become separated and cause
injury or damage.
Electrical installation 67
11
Summary of Contents for ACS880-107
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 107 inverter units Hardware manual ...
Page 2: ......
Page 4: ......
Page 10: ...10 ...
Page 64: ...2 4 5 6 7 8 11 10 3 a b a b b 1 5 a 64 Electrical installation ...
Page 69: ...Electrical installation 109 5 6 4 3 Electrical installation 69 11 ...
Page 70: ...7 a b d c 110 Electrical installation 7 8 8 8 9 9 70 Electrical installation ...
Page 75: ...2 11 b PE 10 7 5 6 8 a 360 grounding detail Electrical installation 75 11 ...
Page 89: ...With FDPI 02 modules OPEN TERMIN ATED 1 1 2 2 OPEN TERMINATED 3 Electrical installation 89 11 ...
Page 90: ...90 ...
Page 96: ...96 ...
Page 110: ...4 5 6 7 8 6 10 10 110 Maintenance ...
Page 118: ...2 3 7 9 a a c c c 6 8 b b d d 11 e e 118 Maintenance ...
Page 121: ...7 a b d c 110 Electrical installation 7 8 8 8 9 9 Maintenance 121 ...
Page 130: ...130 ...
Page 154: ...154 ...
Page 155: ...Circuit diagrams Refer to the circuit diagrams delivered with the unit 9 Circuit diagrams 155 ...
Page 156: ...156 ...
Page 159: ... Dimension drawing 400 mm wide cubicle R1i R4i 400 mm R6i R7i Dimensions and weights 159 ...
Page 161: ... Dimension drawing R8i without C128 or H353 bottom cable exit Dimensions and weights 161 ...
Page 162: ... Dimension drawing R8i without C128 or H353 top cable exit 162 Dimensions and weights ...
Page 163: ... Dimension drawing 2 R8i without C128 or H353 bottom cable exit Dimensions and weights 163 ...
Page 164: ... Dimension drawing 2 R8i without C128 or H353 top cable exit 164 Dimensions and weights ...
Page 165: ... Dimension drawing 3 R8i without C128 or H353 bottom cable exit Dimensions and weights 165 ...
Page 166: ... Dimension drawing 3 R8i without C128 or H353 top cable exit 166 Dimensions and weights ...
Page 167: ... Dimension drawing drive control unit DCU 300 mm Dimensions and weights 167 ...
Page 169: ...Inverter module cubicle with one R8i module top cable exit Dimensions and weights 169 ...
Page 182: ...182 ...
Page 200: ...200 ...