Refer to the drawing below.
1.
Stop the drive and do the steps in section
Electrical safety precautions (page 57)
before
you start the work.
2.
Remove the shrouding above the module bay (in front of the DC fuses).
3.
Remove the DC fuses and the busbar assembly connecting the fuses to the inverter
module. Store these parts – they are to be reinstalled only with the inverter module.
Make note of the order of washers.
4.
Remove the faulty module from its bay. See the module replacement instructions.
5.
Install the air baffle (included) to the underside of the top module guide:
•
Fasten the front edge of the baffle to the module mounting holes using the module
mounting screws (2 × M8). Tighten to 9 N·m (6.6 lbf·ft).
•
Fasten the left/right sides of the baffle using M4 screws wherever possible. (This
depends on the location of the module in the cubicle.) Tighten to 1…2 N·m
(0.7 … 1.5 lbf·ft).
3
5
6.
If the inverter control unit (A41) is powered from the faulty module, connect the power
supply wiring to another module using the extension wire set included.
7.
If the Safe torque off (STO) function is in use, install the jumper wire set included in the
STO wiring in place of the missing module. (This is not needed if the module was the
last on the STO wire chain.)
8.
Reinstall all shrouding removed earlier.
Note:
Do not reinstall the DC fuses or busbars but store them elsewhere until the module
can be reinstalled.
9.
Switch on the power to the drive.
10. Enter the number of inverter modules present into parameter
95.13 Reduced run mode
.
11. Reset all faults and start the drive.
12. If the Safe torque off (STO) function is in use, perform an acceptance test. See the STO
instructions.
124 Maintenance
Summary of Contents for ACS880-107
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 107 inverter units Hardware manual ...
Page 2: ......
Page 4: ......
Page 10: ...10 ...
Page 64: ...2 4 5 6 7 8 11 10 3 a b a b b 1 5 a 64 Electrical installation ...
Page 69: ...Electrical installation 109 5 6 4 3 Electrical installation 69 11 ...
Page 70: ...7 a b d c 110 Electrical installation 7 8 8 8 9 9 70 Electrical installation ...
Page 75: ...2 11 b PE 10 7 5 6 8 a 360 grounding detail Electrical installation 75 11 ...
Page 89: ...With FDPI 02 modules OPEN TERMIN ATED 1 1 2 2 OPEN TERMINATED 3 Electrical installation 89 11 ...
Page 90: ...90 ...
Page 96: ...96 ...
Page 110: ...4 5 6 7 8 6 10 10 110 Maintenance ...
Page 118: ...2 3 7 9 a a c c c 6 8 b b d d 11 e e 118 Maintenance ...
Page 121: ...7 a b d c 110 Electrical installation 7 8 8 8 9 9 Maintenance 121 ...
Page 130: ...130 ...
Page 154: ...154 ...
Page 155: ...Circuit diagrams Refer to the circuit diagrams delivered with the unit 9 Circuit diagrams 155 ...
Page 156: ...156 ...
Page 159: ... Dimension drawing 400 mm wide cubicle R1i R4i 400 mm R6i R7i Dimensions and weights 159 ...
Page 161: ... Dimension drawing R8i without C128 or H353 bottom cable exit Dimensions and weights 161 ...
Page 162: ... Dimension drawing R8i without C128 or H353 top cable exit 162 Dimensions and weights ...
Page 163: ... Dimension drawing 2 R8i without C128 or H353 bottom cable exit Dimensions and weights 163 ...
Page 164: ... Dimension drawing 2 R8i without C128 or H353 top cable exit 164 Dimensions and weights ...
Page 165: ... Dimension drawing 3 R8i without C128 or H353 bottom cable exit Dimensions and weights 165 ...
Page 166: ... Dimension drawing 3 R8i without C128 or H353 top cable exit 166 Dimensions and weights ...
Page 167: ... Dimension drawing drive control unit DCU 300 mm Dimensions and weights 167 ...
Page 169: ...Inverter module cubicle with one R8i module top cable exit Dimensions and weights 169 ...
Page 182: ...182 ...
Page 200: ...200 ...