Guidelines for planning the electrical installation 55
Additional data for calculating the rise time and the peak line-to-line voltage
If you need to calculate the actual peak voltage and voltage rise time considering the
actual cable length, proceed as follows:
•
Peak line-to line voltage: Read the relative
Û
LL
/
U
N
value from the appropriate diagram
below and multiply it by the nominal supply voltage (
U
N
).
•
Voltage rise time: Read the relative values
Û
LL
/
U
N
and (du/dt)/
U
N
from the appropriate
diagram below. Multiply the values by the nominal supply voltage (
U
N
) and substitute
into equation
t
= 0.8 ·
Û
LL
/(du/dt).
Additional note for sine filters
Sine filters protect the motor insulation system. Therefore, du/dt filter can be replaced with
a sine filter. The peak phase-to-phase voltage with the sine filter is approximately 1.5 ·
U
N
.
A
Drive with du/dt filter
B
Drive without du/dt filter
I
Motor cable length
Û
LL
/
U
N
Relative peak line-to-line voltage
(du/dt)/U
N
Relative du/dt value
Note
:
Û
LL
and du/dt values are approximately 20% higher with resistor braking.
Û
LL
/
U
N
l
(m)
du/dt
UN
-------------(1/
s)
1.0
2.0
5.0
4.0
3.0
1.5
2.5
3.5
4.5
100
200
300
100
200
300
0.0
0.5
1.0
1.5
2.0
2.5
3.0
l
(m)
du/dt
UN
-------------(1/
s)
Û
LL
/
U
N
5.5
A
B
Summary of Contents for ACS880-07C
Page 1: ... ABB INDUSTRIAL DRIVES Hardware manual ACS880 07C drives 45 to 710 kW 50 to 700 hp ...
Page 4: ......
Page 12: ...12 ...
Page 74: ...74 Electrical installation PE PE 8 PE 13 11 7 8 12 13 ...
Page 88: ...88 Electrical installation ...
Page 98: ...98 Control unit of frames R6 to R9 ...
Page 110: ...110 Fault tracing ...
Page 125: ...Maintenance 125 7 Install the sliding rail ...
Page 132: ...132 Maintenance 9 Fasten the extraction ramp to the cabinet base with two screws 9b 9a ...
Page 136: ...136 Maintenance ...
Page 148: ...148 Technical data R6 Input and output cable terminal size incoming switch OT160 ...
Page 149: ...Technical data 149 R7 Input and output cable terminal size incoming switch OT160 OT250 ...
Page 150: ...150 Technical data R8 Input and output cable terminal size incoming switch OT160 OT250 ...
Page 151: ...Technical data 151 R7 Input and output cable terminal size incoming switch OT315 ...
Page 152: ...152 Technical data R8 Input and output cable terminal size incoming switch OT315 ...
Page 153: ...Technical data 153 R9 Input and output cable terminal size incoming switch OT315 OT400 ...
Page 154: ...154 Technical data R9 Input and output cable terminal size incoming switch OT630 ...
Page 155: ...Technical data 155 R6 R7 R8 Input cable terminal size incoming switch OT160 OT250 option F250 ...
Page 156: ...156 Technical data R7 R8 Input cable terminal size incoming switch OT315 option F250 ...
Page 157: ...Technical data 157 R9 Input cable terminal size incoming switch OT315 OT400 option F250 ...
Page 158: ...158 Technical data R9 Input cable terminal size incoming switch OT630 option F250 ...
Page 159: ...Technical data 159 R6 R7 R8 Output cable terminal size DU DT filter option E205 ...
Page 160: ...160 Technical data R9 Output cable terminal size DU DT filter option E205 ...
Page 161: ...Technical data 161 R10 Input and output cable terminal size ...
Page 162: ...162 Technical data ...
Page 163: ...Technical data 163 ...
Page 164: ...164 Technical data R11 Input and output cable terminal size ...
Page 165: ...Technical data 165 ...
Page 166: ...166 Technical data ...
Page 172: ...172 Technical data ...
Page 174: ...174 Dimension drawings Frame sizes R6 to R8 ...
Page 175: ...Dimension drawings 175 Frame size R9 ...
Page 176: ...176 Dimension drawings Frame size R10 ...
Page 177: ...Dimension drawings 177 Frame size R11 ...
Page 178: ...178 Dimension drawings ...
Page 180: ...180 Safe torque off function ...