Guidelines for planning the electrical installation 49
5
Guidelines for planning the
electrical installation
Contents of this chapter
This chapter contains instructions for planning the electrical installation of the drive. Some
instructions are mandatory to follow in every installation, others provide useful information
that only concerns certain applications.
Limitation of liability
The installation must always be designed and made according to applicable local laws and
regulations. ABB does not assume any liability whatsoever for any installation which
breaches the local laws and/or other regulations. Furthermore, if the recommendations
given by ABB are not followed, the drive may experience problems that the warranty does
not cover.
Selecting the supply disconnecting device
The drive is equipped with a main switch-disconnector as standard. The disconnector can
be locked to the open position for installation and maintenance work.
Selecting the main contactor
The drive can be equipped with a line contactor (F250).
Summary of Contents for ACS880-07C
Page 1: ... ABB INDUSTRIAL DRIVES Hardware manual ACS880 07C drives 45 to 710 kW 50 to 700 hp ...
Page 4: ......
Page 12: ...12 ...
Page 74: ...74 Electrical installation PE PE 8 PE 13 11 7 8 12 13 ...
Page 88: ...88 Electrical installation ...
Page 98: ...98 Control unit of frames R6 to R9 ...
Page 110: ...110 Fault tracing ...
Page 125: ...Maintenance 125 7 Install the sliding rail ...
Page 132: ...132 Maintenance 9 Fasten the extraction ramp to the cabinet base with two screws 9b 9a ...
Page 136: ...136 Maintenance ...
Page 148: ...148 Technical data R6 Input and output cable terminal size incoming switch OT160 ...
Page 149: ...Technical data 149 R7 Input and output cable terminal size incoming switch OT160 OT250 ...
Page 150: ...150 Technical data R8 Input and output cable terminal size incoming switch OT160 OT250 ...
Page 151: ...Technical data 151 R7 Input and output cable terminal size incoming switch OT315 ...
Page 152: ...152 Technical data R8 Input and output cable terminal size incoming switch OT315 ...
Page 153: ...Technical data 153 R9 Input and output cable terminal size incoming switch OT315 OT400 ...
Page 154: ...154 Technical data R9 Input and output cable terminal size incoming switch OT630 ...
Page 155: ...Technical data 155 R6 R7 R8 Input cable terminal size incoming switch OT160 OT250 option F250 ...
Page 156: ...156 Technical data R7 R8 Input cable terminal size incoming switch OT315 option F250 ...
Page 157: ...Technical data 157 R9 Input cable terminal size incoming switch OT315 OT400 option F250 ...
Page 158: ...158 Technical data R9 Input cable terminal size incoming switch OT630 option F250 ...
Page 159: ...Technical data 159 R6 R7 R8 Output cable terminal size DU DT filter option E205 ...
Page 160: ...160 Technical data R9 Output cable terminal size DU DT filter option E205 ...
Page 161: ...Technical data 161 R10 Input and output cable terminal size ...
Page 162: ...162 Technical data ...
Page 163: ...Technical data 163 ...
Page 164: ...164 Technical data R11 Input and output cable terminal size ...
Page 165: ...Technical data 165 ...
Page 166: ...166 Technical data ...
Page 172: ...172 Technical data ...
Page 174: ...174 Dimension drawings Frame sizes R6 to R8 ...
Page 175: ...Dimension drawings 175 Frame size R9 ...
Page 176: ...176 Dimension drawings Frame size R10 ...
Page 177: ...Dimension drawings 177 Frame size R11 ...
Page 178: ...178 Dimension drawings ...
Page 180: ...180 Safe torque off function ...