366 Fault tracing
42F1
IGBT temperature
Drive IGBT temperature is
excessive.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive power.
4310
Excess temperature
Power unit module
temperature is excessive.
See
).
4380
Excess temperature
difference
High temperature difference
between the IGBTs of different
phases.
See
).
4981
External temperature
1
(Editable message text)
Measured temperature 1 has
exceeded fault limit.
Check the value of parameter
Check the cooling of the motor (or other
equipment whose temperature is being
measured).
Check the value of parameter
4982
External temperature
2
(Editable message text)
Measured temperature 2 has
exceeded fault limit.
Check the value of parameter
Check the cooling of the motor (or other
equipment whose temperature is being
measured).
Check the value of parameter
5080
Fan
Cooling fan feedback missing.
See
(page
5081
Auxiliary fan not
running
An auxiliary cooling fan
(connected to the fan
connectors on the control unit)
is stuck or disconnected.
See
(page
).
5090
DIL hardware failure
Drive interlock hardware
failure.
Contact your local ABB representative,
quoting the auxiliary code. The code
contains location information, especially
with parallel-connected inverter modules.
When converted into a 32-bit binary
number, the bits of the code indicate the
following:
31…28: Number of faulty inverter module
(0…11 decimal). 1111: DIL_ACT states of
control unit and inverter modules in
conflict
27: DIL_ACT state of inverter modules
26: DIL_ACT state of control unit
25: DIL1 of control unit
24: DIL2 of control unit
23…12: DIL1 of inverter modules 12…1
(Bits of non-existing modules set to 1)
11…0: DIL2 of inverter modules 12…1
(Bits of non-existing modules set to 1)
5091
Drive interlock
Drive interlock function is
active, i.e. safety circuit
signal(s) connected to
connector XDIL is broken
during start or run.
Check Drive interlock circuit connections.
For more information, see appropriate
drive hardware manual and description of
parameter
(page
).
Code
(hex)
Fault
Cause
What to do
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...