204 Parameters
Selects which indications are given when one or both Drive
interlock (DIL) signals are switched off or lost. The indications
also depend on whether the drive is running or stopped when
this occurs.
The tables at each selection below show the indications
generated with that particular setting.
Notes:
• This parameter does not affect the operation of the DIL
function itself. The DIL function will operate regardless of
the setting of this parameter: a running drive will stop upon
removal of one or both DIL signals, and will not start until
both DIL signals are restored and all faults reset.
• The loss of only one DIL signal always generates a fault as
it is interpreted as a malfunction.
• This parameter cannot be changed while the drive is
running.
For more information on the DIL, see the
Hardware manual
of
the drive.
Fault/Fault
0
Fault/Warning
1
No.
Name/Value
Description
Def
/
FbEq16
Inputs
Indication (running or stopped)
IN1
IN2
0
0
Fault
0
1
Faults
and
1
0
Faults
and
1
1
(Normal operation)
Inputs
Indication
IN1
IN2
Running
Stopped
0
0
Fault
Warning
0
1
Warning
1
0
Warning
1
1
(Normal operation)
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...